Calibration

Remove the housing cover.

To increase the set point at which the No. 1 (left side) switching element(s) actuates,

turn the hex adjusting nut clockwise with a 3/4-inch open-end wrench.

Sight across the flat top of the adjusting nut to the calibration scale at the bottom of

the housing for an approximate set point. Use a 1/4% external pressure gauge to more
precisely calibrate the pressure switch.

Repeat steps

and

for the No. 2 (right side) set point. There is no interaction, so it

is not critical whether the left or right side is set first.

Replace the housing cover. The pressure switch can be placed in service.

Overtravel has been preset at the factory, i.e. the switching element assembly has
been precisely positioned in the housing for optimum performance. It normally
should not be changed in the fi eld. Should adjustment be necessary, factory
approved procedures must be closely followed. Any inadvertent movement or
replacement in the fi eld will degrade performance, void the warranty and could
render the device inoperative.

“V2 EXPLOSION PROOF 18”

18 AWG color-coded and marked wire leads

with 3/4” NPT (F) conduit connection.

Common

Normally Open

Normally Closed

SPDT

No. 1 (Left side)

C1 Blue

NO1 Black

NC1 Red

No. 2 (Right side)

C2 Blue

NO2 Black

NC2 Red

2-SPDT (DPDT)

Nos. 1 & 2 (Left side)

C1 Blue

NO1 Black

NC1 Red

C2 Yellow

NO2 Brown

NC2 Orange

Nos. 3 & 4 (Right side)

C3 Blue

NO3 Black

NC3 Red

C4 Yellow

NO4 Brown

NC4 Orange

GR - Ground (Earth) Green wire connected to each hermetically sealed switching
element capsule.

NOTE: Transpose NO and NC on vacuum switches when set points are in the vacuum range.