Set point ok, Contacts open - set point too high, Contacts closed - set point too low – SOR Single Diaphragm Weatherproof Differential Pressure Switch with Terminal Block Connections User Manual

Page 6

Advertising
background image

6/12

Form 506 (01.13) ©SOR Inc.

Set Point OK

If contacts break precisely at critical decreasing
differential pressure set point, repeat steps

-

as desired to verify calibration.

Calibration is complete.

Normal Operating

Differential Pressure

Make

Critical Decreasing

Set Point

Differential Pressure

Break

Contacts Open - Set Point Too High

If contacts are open when critical decreasing
differential pressure is reached, turn set point
adjustment counterclockwise (out) until contacts make.
From this point, turn set point adjustment clockwise
(in) until contacts break. Repeat Steps

-

.

Make

Break

Normal Operating

Differential Pressure

Contacts Closed - Set Point Too Low

If contacts are closed when critical increasing
differential pressure is reached, turn set point
adjustment clockwise (in) until contacts break.
Repeat Steps

-

.

Break

Normal Operating

Differential Pressure

Critical Decreasing

Set Point

Make

0 Time

Critical Decreasing

Set Point

Differential Pressure

Differential Pressure

For Critical Set Point on Decreasing Differential Pressure

Connect the continuity test lamp or ohmmeter across the C - Common and NO - Normally

Open contacts.

Close the bleed valve(s), open the equalizer valve, and raise pressure equally on both HI

and LO sides to the normal operating high side pressure.

With normal HI side pressure stable, close the equalizer valve to isolate the HI side from

the LO side.

Slightly open the LO side bleed valve to reduce LO side pressure (increase differential

pressure) until the normal operating differential pressure appears on the digital indicator.
Close the bleed valve to stabilize differential pressure. Contacts should close (make) by
the time normal operating differential pressure is reached. If the contacts are still open
at normal operating differential pressure, turn the set point adjustment counterclockwise
(out) until the contacts make.

Keeping the high side pressure steady, slightly open the equalizer valve to increase LO side

pressure (decrease differential pressure) until the desired differential pressure set point
appears on the digital indicator. Close the equalizer valve to stabilize differential pressure.
Check the status of the electrical contacts against the following differential pressure trend
graphs. Follow the instructions under the graph that matches the status of the contacts.