Electrical connection (remote self-test) – SOR Single Point Ultrasonic Level Switch User Manual

Page 6

Advertising
background image

6/20

Form 771 (08.13) ©SOR Inc.

Electrical Connection (Remote Self-Test)

Ensure that wiring comforms to all
applicable local and national
electrical codes and install unit(s)
according to relevant national and
local safety codes.

Make sure the power source is

turned

off.

Remove the housing cover.

Explosion Proof and Non-Agency Listed models:

TB2 Remote Self-Test Terminal Block
(Non-Intrinsically Safe Units Only)

TB1

Loop Power Terminal Block

Remote Dry Contact

Ground Twisted Pair Shield
to Housing Ground Screw

1800
1700
1600
1500
1400
1300
1200
1100
1000

900
800
700
600
500
400
300
200
100

0

Power Supply Voltage (Volts)

5 10 15 20 25 30 35 40

Maximum Loop Resistance (Ohms)

(including Barrier Resistance)

Loop Resistance vs. Power Supply Voltage

1 Ohm at

11 VDC

850 Ohms

at 28 VDC

650 Ohms

at 24 VDC

950 Ohms

at 30 VDC

1450 Ohms

at 40 VDC

Electrical power must be disconnected from explosion proof models before
the cover is removed. Failure to do so could result in severe personal injury
or substantial property damage.

Pull twisted pair cable through the conduit connection and into the control housing.

Connect dry contact wires to TB2 on the control board. (See

) Terminals are

labeled “RMT COM” and “RMT TST*”. Attach the twisted pair shield to the ground

screw inside the housing. Ground only one end of the twisted pair shield.

Do not apply power to the remote test terminals.

Connect the open end of the wires to a dry (unpowered) contact designed for small

loads. There is no polarity required for this connection.