Dimensions, Maintenance, Troubleshooting – SOR 1780 Wireless Level Switch User Manual

Page 3: Symptom probable cause

Advertising
background image

Form 1564 (09.14) ©SOR Inc.

3/4

Dimensions

Linear = mm/inches

Drawing 0390759

131.4

5.17

207.3

8.16

36.3

1.43

72.7

2.86

50.8

2.00

50.8

2.00

WRENCH

FLATS

64.5 REF

2.54

128.9 REF

5.08

89.3 REF

3.52

NAMEPLATE

2" NPTM

PROCESS

CONNECTION

FLOAT

Maintenance

 Clean the float and counterweight mechanism periodically to assure continued free

movement.

 Make no adjustments to the float or counterweight mechanism. They are factory

calibrated for optimum performance.

Troubleshooting

Symptom

Probable Cause

The control will not function
when installed but operates
when removed from process
connection.

a. Float travel is inadequate. Check for internal
vessel obstructions. See Mounting Requirements.

Liquid is in the vessel at the
actuation level but the unit
does not respond.

a. The float pivot pin is bound up or dirty. Clean the
float pivot pin.
b. The specific gravity of the liquid is not sufficient
to lift the float.
c. The float is leaky or collapsed. Contact the factory.