Ta housing – SOR TA Nuclear Qualified Temperature Switch User Manual

Page 4

Advertising
background image

4/8

Form 655 (04.13) ©SOR Inc.

TA Housing

Mounting Hardware Fasteners per SOR Test Report 9058-102 consist of three standard-
grade 1/4-inch U bolts (not supplied).

Maintenance Replace cover o-rings (SOR P/N 8923-206 and 8923-207) whenever cover
is removed or minimum of once every 5 years, whichever comes first. Unscrew the cover.
Remove the old o-rings. Place new o-rings in grooves of cover. Lubricate o-rings with
light film of Krytox 240AC grease (or equivalent fluorinated grease). Tighten cover until the
flange of the cover makes contact with the housing.

Cover

1/4” NPT(F)
Vent Connection

Body

Process Connection

Sensing Bulb

U-Bolts

3/4” NPT(F)

Conduit

Connection

Cover

Sensing

Bulb

Process

Connection

Gland Nut

Capillary

U-Bolts

3/4” NPT(F)

Conduit Connection

Retainer

1/4” NPT(F)

Vent

Connection

Remote Mount

Direct Mount

Advertising