Spectrum Controls 1746sc-NI8u User Manual

Page 78

Advertising
background image

66

SLC 500

Universal Analog Input Module

Channel Error (Bit 15)

The module sets this fault bit when it detects any of the following:

Configuration erorrs:

- configuration bits Data Format definition, invalid Input Types for

channels 0 through 3: 10010 - 11101

- configuration bits Data Format definition of Engineering Units x 1 for

Input Types of ±500mV, 0-5V, 1-5V, 0-10V, ±10V, 0-20mA

- configuration bits where Open Circuit is enabled with Input types of 0-

5V, 1-5V, 0-10V, ±10V, or 0-20mA

- invalid data acquisition of an input channel

- the filter frequency selected for the valid channel currently fails

autocalibration range checks

Module Status LED (Green)

The module-status LED indicates when the module detects a
nonrecoverable fault at power up or during operation. For this type of
fault, the module:

• no longer communicates with the SLC processor

• disables all channels

• clears all data and status words

A module failure is non-recoverable and requires the assistance of your
local distributor or Spectrum Controls.

Interpreting I/O Error

Codes

I/O error codes appear in word S:6 of the SLC processor status file. The
first two digits of the error code identify the slot (in hexadecimal) with the
error. The last two digits identify the I/O error code (in hexadecimal).

The error codes that apply to your module include (in hexadecimal):

• 50–5E

• 71 (watchdog error)

• 90–94

For a description of the error codes, refer to the Allen-Bradley Advanced
Programming Software (APS) Reference Manual
, Allen-Bradley
publication 1746-6.11.