CLW QUAD SERIES CHILLER INSTALLATION MANUAL

Power Fail Restart

When the controller is first powered up, the outputs will

be disabled and delay timers reset to avoid a random

start or multiple compressors staring simultaneously.

Lead Compressor Start Delay Time

The lead compressor Fixed-On-Delay-Time that will

ensure that the lead compressor output is not enabled

for 120 seconds after the control receives a call to start

the unit and the lead compressor.

This delay is not adjustable.

Lag Compressor Start Delay Time

The lag compressor Fixed-On-Delay-Time will ensure

that the lead compressor output is not enabled for 5

minutes after the control receives a call to start the

lead compressor.

This delay is adjustable from 60 – 3600 seconds over a

BAS or a local display.

Compressor Minimum On Delay

There is no compressor minimum on time safety but in

adjusting the on off dead band for any given site no

compressor should never be enabled for less than two

(2) minutes each time the compressor output is enabled.

Compressor Minimum Off Delay Time

The compressor minimum time delay will ensure

that the compressor output will not be enabled for a

minimum of ten (10) minutes after it is disabled.

This allows for the system refrigerant pressures to

equalize after the compressor is disabled.

This delay is adjustable from 480 - 1200 over a BAS or

a local display.

Compressor Lead/Lag

Compressor lead/lag is a standard part of the

system. The unit is shipped from the factory with lead/

lag disabled.

Lead/lag can be activated through the unit from the

user interface.

Modes

The flowing modes are supported. Optional dual 6-pipe

rack* or local valves are required to implement many of

the modes

Heating Only Cycle

Cooling Only Cycle

Simultaneous Heating and Cooling*

Fixed Building Heating and Cooling*

Primary Heating Secondary Cooling*

Primary Cooling Secondary Heating*

• Free

Cooling*

Fault History

If a fault occurs the fault will be recorded and

displayed on the local display and an enumerated

status is available for the BAS.

Optional trending and archiving solutions are available.