FAULT Output

The STR drives feature a digital FAULT output. This output closes

to signal a fault condition.

This output can be used to drive LEDs, relays and the inputs of

other electronic devices like PLCs. The “+” (collector) and “-” (emitter) terminals of the output

transistor are available at the connector. This allows you to configure the output for current

sourcing or sinking.

Diagrams of each type of connection follow.

Do not connect the output to more than 30VDC.

The current through the output terminal must not exceed 80 mA.

Sinking Output

STR

5-24 VDC

Power Supply

+

Load

FAULT-

FAULT+

!

STR

5-24 VDC

Power Supply

+

Load

FAULT-

FAULT+

Sourcing Output

Driving a Relay

STR

FAULT-

FAULT+

1N4935 suppression diode

5-24 VDC

Power Supply

+

relay

FAULT+

FAULT-