POWER NET

M98146001-03-11C

5

TECHNICAL FEATURES

Measured current
WG-35

50 / 100 / 250 (A)

WG-70

500 / 1000 (A)

Electrical features
Maximum voltage

720 V c.a

Isolation voltage

3.000 V c.a

Supply
L1-L2 :

400 V c.a. AC

Voltaje tolerance

-15 % / +10 %

Frequency

50…60 Hz

Consumption:

4,2 VA

Measure

300 V c.a AC (f-n)

Nominal voltage

520 V c.a. AC (f-f)

Frequency

45…65 Hz

Nominal current

(según transformador)

Permanent overload

1,2 In

Voltage circuit consumption

0,75 V·A

Mechanical and enviromental
Material

Plastic V0 self-extinguishing

Protection

IP 20

Dimensions (mm)

165 x 73 x 33

weight

0.220 kg

Work temperature

-10º…50 º C

Altitude

2.000 m

Humidity (without condensation) :

5%...95%

Accuracy
Voltage

0.5 % ± 2 digit

Current

0.5 % ± 2 digit

Power

1 % ± 2 digit

Measure condition without current transformers and direct voltage
Temperature

+ 5 … + 45 ºC

Power Factor

0,5…1

Measure range to end scale

10...100 %

Safety
Category III - 300 V c.a. / 520 c.a. EN-61010 Electric shock protection by double
isolation class II
Standards
IEC 664, UL 94, VDE 0414 IEC 664, VDE 0110, UL 94, IEC 801, IEC 348, IEC 571-
1, EN 61000-6-3, EN 61000-6-1, EN-61010-1

6

COMMUNICATIONS

The MEMORY MAP table shows the memory map addresses of each variable
that measures and calculates the analyzer and it’s code.

6.1

PERIPHERAL NUMBER AND BAUDRATE

It’s possible through a Modbus command to configure the device. The memory
locations that are changed are in the next table:

Modbus address

Modified variable

Valid range

3000, 3001

Device serial number

0 a 999999999

3002H

Peripheral number

1 a 255

3002L

Speed (baud rate)

0= 9600, 1= 19200


The Modbus command to send is (hex.):

Tx: 00100BB8000306NNNNNNNNPPVVCRC
Rx:

There is no answer in broadcast frame.


This command sets the peripherals number and the baud rate of communications
for devices connected in the same network that have the default peripheral
number. The command is sent to the peripheral number 0 (broadcast) to interpret
all devices, but only make the change the device that matches the serial number
is sent as parameter. The peripheral number and communications port speed be
set immediately, without requiring a reset of the device.

6.2

RS-485 LAYOUT

The picture shows how to connect a communication bus between multiple Power
Net. The converter can be RS-485 to RS-232 serial port or Ethernet depending
on the facility infrastructure. The standard RS-485 connection allows a maximum
of up to 32 peripherals in each bus.

CONEXION RS-485

6.3

MEMORY MAP

VARIABLE

SYMBOL COD

INST

MÁX

MÍN

UNITS

Phase voltage

V 1

1

00-01

60-61

C0-C1

V x10

Current

A 1

2

02-03

62-63

mA

Active Power

Kw 1

3

04-05

64-65

W

Reactive Power

Kvar 1

4

06-07

66-67

W

Power factor

PF 1

5

08-09

68-69

C8-C9

x100

Phase voltage

V 2

6

0A-0B

6A-6B

CA-CB

V x10

Current

A 2

7

0C-0D

6C-6D

mA

Active Power

Kw 2

8

0E-0F

6E-6F

W

Reactive Power

Kvar 2

9

10-11

70-71

W

Power factor

PF 2

10

12-13

72-73

D2-D3

x100

Phase voltage

V 3

11

14-15

74-75

D4-D5

V x10

Current

A 3

12

16-17

76-77

mA

Active Power

Kw 3

13

18-19

78-79

W

Reactive Power

Kvar 3

14

1A-1B

7A-7B

W

Power factor

PF 3

15

1C-1D

7C-7D

DC-DD

x100

Active Power III

Kw III

16

1E-1F

7E-7F

W

Inductive Power III

KvarL III

17

20-21

80-81

W

Capacitive Power III

KvarC III

18

22-23

82-83

W

Cos φ III

Cos φ III

19

24-25

84-85

E4-E5

x100

Power factor III

PFIII

20

26-27

86-87

E6-E7

x100

Frequency (L1)

Hz

21

28-29

88-89

E8-E9

Hz x10

Line voltage L1-L2

V12

22

2A-2B

8A-8B

EA-EB

V x10

Line voltage L2-L3

V23

23

2C-2D

8C-8D

EC-ED

V x10

Line voltage L3-L1

V31

24

2E-2F

8E-8F

EE-EF

V x10

%THD V 1

%THDV1

25

30-31

90-91

% x 10

%THD V 2

%THDV2

26

32-33

92-93

% x 10

%THD V 3

%THDV3

27

34-35

94-95

% x 10

%THD I 1

%THDI1

28

36-37

96-97

% x 10

%THD I 2

%THDI2

29

38-39

98-99

% x 10

%THD I 3

%THDI3

30

3A-3B

9A-9B

% x 10

Active Energy

Kwh III

31

3C-3D

Wh

Ind. Reactive Energy

KvarhL III

32

3E-3F

Wh

Cap. Reactive Energy

KvarhC III

33

40-41

Wh

Apparent Power III

KvaIII

34

42-43

A2-A3

W

Maximum Demand

Md(Pd)

35

44-45

A4-A5

W/VA/mA

Average current

I_AVG

36

46-47

A6-A7

mA

Neutral current

In

37

mA

Maximum Demand I2

Md(Pd)

42

52-53

B2-B3

mA

Maximum Demand I3

Md(Pd)

43

54-55

B4-B5

mA

7

ASSITANCE SERVICE

In case of operational doubt or equipment breakdown, call CIRCUTOR’s
Customer Service.
CIRCUTOR, S.A. – Customer Service
Vial Sant Jordi, s/n
08232 -Viladecavalls (Barcelona)
National phone

902 449 459

International phone: (+34) 93 745 29 00
fax – (+34) 93 745 29 14
E-mail :

[email protected]

Advertising