CIRCUTOR TCP1RS+ User Manual

Page 2

Advertising
background image

TCP1RS+

M98253301-03-14A



3.- TECHNICAL FEATURES

Power circuit:

-

Single-phase (A1 – A2) :

-

Frequency:

-

Maximum consumption:

-

Working temperature:

-

Humidity (no condensation) :

230 V

ac

± 15%

47…63 Hz

8 VA

-10 … +60 ºC

5 … 95%

LED symbols:

-

Flashing power LED

-

Flashing RX/TX

-

LINK/ACTIVITY

Powered unit and CPU activity

RS-485 frame delivery and reception activity

Flashing: Activity in the Ethernet bus

Green: Speed 10/100 Mb/s

Mechanical features:

-

Case material:

-

Unit protection degree:

-

Dimensions (mm):

-

Weight:

-

Maximum operating height:

UL94 - V0 self-extinguishing plastic

IP 20

35.4 x 73 x 84.68 mm (2 modules)

120 g

2,000 m

Standards:

IEC 60664, VDE 0110, UL 94, EN61010-1, EN55011, EN 61000-4-2, EN 61000-4-3,

61000-4-11, EN 61000-6-4, EN 61000-6-2, EN 61000-6-1, EN 61000-6-3, EN 61000-4-5,

CE

Network interface:

-

Type:

-

Connector:

-

Network Protocols - Accesses:

Ethernet 10BaseT / 100BaseTX self-detecting

RJ45

TCP / UDP / Modbus

Safety:

Installation category: Category III / EN61010 double-insulated electric shock protection

class II. The unit must be connected to a power circuit protected with type gl fuses, in

compliance with IEC 269, or type M, with values from 0.5 to 1A. It must be fitted with a

circuit breaker switch or equivalent device in order to be able to disconnect the unit from

the power supply. The power supply cable must have a minimum cross-section of 1 mm

2

.

If the unit is not operated according to the manufacturer's specifications, its guaranteed

degree of protection may be compromised.

Serial interface:

-

Type:

-

Transmission speed (configurable):

-

Data bits:

-

Parity:

-

Stop bit

RS-485 three-wires (A/S/B) (RX/GND/TX)

1200, 2400, 4800, 9600,19200, 34800, 57600,

115200 baud rate

7, 8

No parity, odd, even

1 or 2

4.- CONNECTIONS

Figure 1. Standard connection of serial units

5.- TECHNICAL SERVICE

If you have any doubts about the operation of the unit or suspect any malfunction, contact our service staff at CIRCUTOR, SA

CIRCUTOR, SA - Technical Assistance Service

Vial Sant Jordi, s/n

08232 – Viladecavalls (Barcelona), SPAIN

Tel.: 902 449 459 (Spain)

Tel.: (+34) 93 745 29 00 (Outside Spain)
email:

[email protected]

Advertising