6.5. Communications description

One or more EDMk meters can be connected to a computer or PLC. As well as the usual operation of each piece of
equipment, this system may centralize data at one single point. The EDMk has an RS-485 series communications
output. If more than one analyzer is connected to one RS-485 communication bus, it is necessary to assign to each a
peripheral address (from 01 to 255) so that the remote computer or PLC sends data on different measured or calculated
recordings to those addresses. The RS-485 connection is made with woven mesh shielded communications cables,
with a minimum of three wires and with a maximum distance between remote computer and the last analyzer of 1.200
metres. This RS-485 series bus can connect up to a maximum of 32 devices.The EDMk meter communicates using the
MODBUS RTU© protocol (Pulling Question / Answer).

7. DISPLAY / LEDS

-

L1

-,

L2

- and

L3

- shows that the device has measured voltage in each phase. If one of these does not exist, the corresponding identifi cation number does not

appear. The symbols appearing behind each phase (L) indicate the direction of the current in the current transformers, showing if the point of measurement
is consuming or generating energy (

L1

,

L2

and

L3

fl ashing, informs of possible errors of connection of current transformers).

-

T1

,

T2

y

T3

(identifi cation only available on the EDM3k; shows the tariff selected for that time, independently from the tariff displayed on the upper

section.
- The

symbol indicates that load is inductive. The

symbol indicates a capacitive load.

- The

symbol shows that the meter is the fi rst and fourth quadrant (consumption). The

symbol indicates that the meter is in the second and third

quadrant (generation).

8. CONNECTIONS

9. TECHNICAL CHARACTERISTICS

EDMk-ITF-RS485-C2

Intelligent converter

Ethernet converter

M31751

M54020

M54031 / M54032

BORNES RS-485

BORNES RS-485

RS-485 / RS-232

A (+)

1 (A(

A

B (-)

2 (B)

B

S (GND)

5 (GND)

S

10. TECHNICAL ASSISTANCE SERVICE

In the event of any equipment failure or any operational queries please contact the technical service of CIRCUTOR, SA.
CIRCUTOR, SA. – After sales service.
Vial Sant Jordi s/n
08232 Viladecavalls, Barcelona

EDMk Manual

M98204801-03-11A

Tel.: (+34) 93 745 29 00
Fax: (+34) 93 745 29 14
e-mail: [email protected]

3 or 4 wires (low voltage)

3 wires (2 VT y 2 CT)

MC1-20 (example 200A)

MC1-30 (example 500 A)

L1

L2

L3

min

max Pd

N

max

clear

COMM

CPU

CVM-MINI

reset

N

N

reset energy

N

1 2 3 4 5 6 7 8 9

10 11 12 13 14 15

b

B

a

A

b

B

a

A

V

L1

V

L2

V

L3

S2

P2

S1

P1

S2

P2

S1

P1

POWER SUPPLY

TIPO C.A.

TIPO C.C. & C.A.

Single phase

230 V a.c.

85..265 Va.c./ 95...300 Vd.c

Voltage tolerance

-15 %... +10 %

Frequency

45...65 Hz

0...65 Hz

Maximum burden

5 V·A

Operating temperature

-20 ºC...+60 ºC

-20 ºC...+60 ºC

Humedity (without condensation)

5 %...95 %

Maximum altitude

2.000 m

MECHANICAL FEATURES

Casing material

Self extinguishing VO plastic

Protection assembled device (front)

IP 51

Protection non assembled device

IP 31

Supply and voltage measure wires

Minimum section 1 mm²

Secondary current transformers wires

Minimum section 2,5 mm²

Dimensions (mm)

85 x 52 x 70 (3 steps)

CLASS

Acuracy class in active energy

Class 1 - EN62053-21

Accuracy class in reactive energy

Class 2 - EN62053-23

STANDARDS

EN62052-11, EN62053-21, EN62053-23, EN61010-1

MEASUREMENT CIRCUIT

Rated voltage

300 V a.c. f-N / 500 V a.c. f-f

Frequency

45...65 Hz

Rated current

.../5 or .../1

Permanent overload

1,2 In

Voltage circuit burden per phase

0,3 V·A

Current circuit burden per phase

0,3 V·A at 5 A. ó 0,06 V·A at 1 A

PULSE OUTPUT TRANSISTOR FEATURES

Opto-insulated transistor (open collector)

NPN

Maximum operating voltage

24 V c.c.

Maximum operating current

50 mA

Maximum frequency

5 imp / s

Pulse length

50 ms

TRANSISTOR OUTPUTS CONNECTIONS

Output 1

Terminal 9 - 8

Output 2

Terminal 7 - 8

MAXIMUM COUNTER VALUE

9999999 kW

SAFETY

Category III EN61010-1. Class II double
insulation against electric shock.

TYPE MC3

The EDMk energy meter display is divided into two sections: the fi rst of these (on the upper section) displays the value of the energy meters (Active energy and Inductive
reactive energy or Capacitive). The second shows the measurement, in real time, being taken by the meter at that time.

CPU

CPU led indicates that the device is working right fl ashing in one second intervals.

COMM

COMM led fl ashes quickly in varible intervals when the device is receiving or sending information throught is RS-485 port.

Set A

NS

Display

ND

NS

Setup

Clear

NC

1 2 3 4 5 6 7 8 9

L1

L2

L3

N

1P1

2P1

3P1

1P2

2P2

3P2

COM

2S1

L1

L2

L3

N

1P1

2P1

3P1

1P2

2P2

3P2

1S1

3S1

Set A

NS

Display

ND

NS

Setup

Clear

NC

1

2

3

4

5

6

7

8

9

L1

L2

L3

L1

L2

L3

1S11S22S12S2

1S11S22S12S2

MC1-20

MC1-20

1S11S22S12S2

MC1-20

Set A

NS

Display

ND

NS

Setup

Clear

NC

1

2

3

4

5

6

7

8

9

L1

L2

L3

L1

L2

L3

1S11S22S12S2

1S11S22S12S2

MC1-30

MC1-30

1S11S22S12S2

MC1-30

Advertising