background image

4�4�2�2�- Energy

The

Read function is implemented for these variables.

Table 7: Modbus variables: Energy

Description

Address

Size

Units

Total values

Imported active energy

0x0000

32 bits

Wh

Exported active energy

0x0002

32 bits

Wh

Q1 reactive energy

0x0004

32 bits

varh

Q2 reactive energy

0x0006

32 bits

varh

Q3 reactive energy

0x0008

32 bits

varh

Q4 reactive energy

0x000A

32 bits

varh

Partial values

Partial imported active energy

0x0030

32 bits

Wh

Partial exported active energy

0x0032

32 bits

Wh

Q1 partial reactive energy

0x0034

32 bits

varh

Q2 partial reactive energy

0x0036

32 bits

varh

Q3 partial reactive energy

0x0038

32 bits

varh

Q4 partial reactive energy

0x003A

32 bits

varh

Note: Some MODBUS variables may not be available depending on the CEM energy meter

coupled to the

CEM M-ETH. See4.4.2.7.- Available addresses by unit”

4�4�2�3�- Operating time, cost and KgCO

2

atmospheric emissions

The

Read function is implemented for these variables.

Table 8: Modbus variables: Operating time, costs and KgCO

2

Description

Address

Size

Units

Cost of the partial consumption

0x00C0

32 bits

-

KgCO2 atmospheric emissions of the partial consumption 0x00C2

32 bits

-

Hours of partial operation

0x00C4

32 bits

( 1 decimal place)

Hours of total operation

0x00C6

32 bits

( 1 decimal place)

Note: Some MODBUS variables may not be available depending on the CEM energy meter

coupled to the

CEM M-ETH. See4.4.2.7.- Available addresses by unit”

4�4�2�4�- Instantaneous values

The

Read function is implemented for these variables.

Table 9: Modbus variables: Instantaneous values�

Description

Address

Size

Units

Phase 1 voltage

0x0732

32 bits

V (1 primary decimal place)

Phase 2 voltage

0x0734

32 bits

V (1 primary decimal place)

Phase 3 voltage

0x0736

32 bits

V (1 primary decimal place)

Phase 1 current

0x0738

32 bits

A (2 primary decimal places)

Phase 2 current

0x073A

32 bits

A (2 primary decimal places)

Phase 3 current

0x073C

32 bits

A (2 primary decimal places)

Phase 1 cos φ

0x073E

32 bits

2 decimal places

Phase 2 cos φ

0x0740

32 bits

2 decimal places