Converter / amplifier camo – CIRCUTOR CAMO User Manual

Page 2

Advertising
background image

Converter / Amplifier CAMO

M98237901-20-12C

M54090 - CAMO

OPTOISOLATED MULTISERIE

AMPLIFIER CONVERTER

1.- Features

CAMO is a protocol converter that allows the
communications between RS-232 master and
until 32 peripherals in RS-485 or till 10 devices
in

RS-422.

Allows

to

amplifier

the

communications signal in RS-485 bus to reach
more length of wiring between the master and
the different peripherals. The function of
converter or amplifier is automatically done by
the device by the communications frames
detected.

2.- Caution

Before

making

any

maintenance

operation, connection modification,
repair, etc., you must disconnect the
device from all power supplies. If you

suspect an operational fault in the unit or in its
protection system, remove the unit from service.
Note that when the instrument is switched on, the
terminals may be dangerous when touched an
opening or removing parts may access dangerous
areas. Therefore, the equipment must not be used
until it is properly installed.

The equipment must be connected to a power
supply circuit protected with gl (IEC 269) or type M
fuses between 0.5 and 2 A. It must have an
overload/short circuit switch or equivalent device in
order to disconnect the equipment from the power
supply system. An earth leakage switch or similar
device must be fitted to disconnect the equipment
from the power supply system. The power supply
circuit are connected with a cable with a minimum
diameter of 1 mm².

3.- Installation

Installation of equipment is done on a DIN rail,
leaving all the connections inside an electrical
panel. The unit has a supply LED indicator next
to the power connector that indicates its status.

4.- Connection

Use only the pins indicated for each
wiring. Use more pins than listed will
cause device malfunction.

4.1.- RS-232 to RS 485 converter

DB-9 female

Protocol

Function

1
2
3
4
5
6
7
8
9

-

RS-232
RS-232

-

RS-232/485

-
-

RS-485
RS-485

-

RX

TX

-

GND

-
-

B
A

Table 1

DB9 female connector (located in the supply
side) uses pins 2, 3 and 5 for RS-232 input
(see table 1).
The RS-485 output connection is possible to do
from the DB9 connector (see table 2) or from
the A-B connectors located beside of the
transmission/reception communications LED.

DB-9 male

Protocol

Function

1
2
5

RS-485
RS-485
RS-485

A
B

GND

Table 2

Picture 1

4.2.- RS-485 to RS 485 Amplifier

To use as amplifier you have to connect the
input in pins 5, 8 and 9 (see table 1).
The amplified RS-485 output can be wired from
DB9 as indicates the table 2 (see picture 1).
The RS-485 output through terminals A-B is
like indicates picture 2.

Picture 2

4.3.- RS 422 output

In RS-422 output is necessary to follow the
connections in the table below with pins 5, 6, 7,
8 and 9.

DB-9 male

Protocol

Function

5
6
7
8
9

RS-422
RS-422
RS-422
RS-422
RS-422

GND

TX +
TX -

RX -
RX +

Table 3

The device has two red LED to inform the
serials communications status (see table 4).

Position

Protocol

Function

Up

Down

RS-422 or 485
RS-422 or 485

TX

RX

Table 4

5.- Maintenance

This

device

does

not

require

specific

maintenance. You must ensure that the device
is disconnected before operation.

6.- Technical features

Supply:

- Switched power supply:
AC: 90…260Vac 50…60 Hz
DC: 100…300Vcc.
- Vcc supply:
CC: 10…36 Vcc
- Consumption 2 VA (90V) / 3 VA (260V)
- Working temperature 0..50ºC
- Humidity (non condensing) 5..95%
- Altitude 2000m
Communication:

Baudrate from 600 to 57.600, word size and
Rx/Tx conmutation auto-configured

Mechanical features:

- Box type: Modular.
V0 Plastic self-extinguishing.
- Fixation: Coupled symmetric profile

DIN 46277 (EN-50022)

- Size

: 53 x 90 x 58 mm

(2 Din rail modules– DIN 43 880)


- Weigh : 0,091 kg
Visualization:
Type : Rx, Tx and POWER LED

- Safely CAT III – 300 V c.a.

(EN-61010)

- Protection against electric shock:

double isolation class II

- IP 20
Standards :
EN-61000-6-2, EN-61010

7.- TECHNICAL SERVICE

For

any

inquiry

about

the

instrument

performance or whether any failure happens,
contact to technical service:

Vial Sant Jordi, s/n
08232 Viladecavalls
(Barcelona) Spain
Tel. 902 449 459 (Spain)
Tel. (+34) 93 745 29 00 (Out of Spain)
Fax (+34) 93 745 29 14
e-mail:

[email protected]

web:

www.circutor.com

Advertising