5.7.- TRIP EVENTS

When a circuit breaker has been activated, the LEDs, output contacts and display will indicate

the cause that generated this situation.

5�7�1� EARTH LEAKAGE CURRENT INTENSITY TRIP

LED

ON LED, off.

LEAKAGE LED, fixed.

OUTPUT RELAYS

The

TRIP relay (terminals 13,14,15) changes its status, IΔ >0,85•IΔn, in accord

ance with the programmed times

The

AUX relay (terminals 4,5) only changes its status if it has been configured

as a pre-alarm

DISPLAY

Fixed red screen that shows the leakage with the earth leakage symbol

(

Figure 16

).

Figure 16:Leakage screen

Prealarm symbol when this function has been activated (

Figure 17

).

Figure 17:Leakage with prealarm screen

Note : Press the PROG key to modify the current and trip time. ( refer to sec-

tion

5.6.1)

If the value is off the scale (> 5•IΔn),

OVR and the pre-alarm symbol will be dis

played

(

Figure 18

).

Figure 18: Off the scale screen

20

RGU-2 Earth Leakage Relay