MCB.P and MCB.T

Miniature circuit breaker

with remote-control

The MCB.P or MCB.T are circuit breakers that provides

a combination of overcurrent protection and contactor

functions into the same element. The MCB.T version

incorporates two auxiliary contacts that indicate the state of

the remote control input and of the overcurrent protection.

For the MCB.P and MCB.T version, an auxiliary contact

can be added to the instrument for the indication of an

overcurrent trip or a manual action over the circuit breaker.

As a circuit breaker operation, two trip conditions are

set:

Delayed thermal trip (overload protection).

Quick electromagnetic trip (short-circuit protection).

The remote control function operates over the same

contacts that the circuit breaker does, guarantying the trip

for any case, and avoiding a remote control connection after

a manual or overcurrent trip occurrence.The remote control

function is electro-magnetically carried out by the

application of an excitation voltage during 20 ms between

terminals ON (terminals 1-3) and OFF (terminals 2-3).

A built-in optical indication permits to know the system

state (red = ON, green = OFF) regardless the trip cause.

The protection set has three different positions

according to the trip condition:

Open circuit breaker. Trip due to overload or short-circuit

event; remote control switching on action not allowed. For a

manual switching on, the lever must be moved to the OFF

position and then raised to the ON position.

Closed circuit breaker. A remote control is

allowed.

Open circuit breaker. Manual trip. A remote

control is not allowed.

!

!

!

!

!

RESET position (intermediate between ON & OFF).

ON position.

OFF position.

The MCB.T model incorporates two free-voltage

auxiliary contacts in the remote control module.

These contacts leave through a tree-cable

connector (white, green and brown cables) referred to a

same common point:

White cable: common

and

cables: information about the remote

control state.

ON: closed contact (remote control ON )

OFF: open contact (remote control OFF )

and

white cablse: information about the

lever position ON RESET-OFF.

ON: closed contact (lever at ON )

OFF: open contact (lever at RESET or OFF)

and

cables: information of overcurrent or

earth leakage trip.

Take into account that:

The remote control contact indicates the received

commands regardless the circuit breaker state (ON, OFF,

RESET position).

!

!

!

!

Green

white

Brown

white

Brown

green

The MCB.T must be only controlled by pulse type

signals (20 ms of duration), otherwise, the control

remote module might suffer irreparable damage. The

MCB.T will only be applicable to WRKRT-25T series

differential relays.

ON: closed contact (No trip)

OFF: open contact (earth leakage or overcurrent trip)

MCB.T

Installation

The breaker can be mounted in any position on an EN 50

022 (35 mm wide) top-hat rail..

To install, place the MCB.P with remote control mechanism

on the rail, adjust to the desired position, then lock the rapid

fastening system (see fig. 1 y 2)

fig. 1

fig. 2

The unit caneasily be removed from its mounting position

retrospectively, if required, by releasing the rapid fastening

system with a screwdriver (see fig. 3)

fig. 3

Vial Sant Jordi, s/n

08232 Viladecavalls

Barcelona (

Spain)

Tel. (+34) 93 745 29 00

Fax

93 745 29 13 (export)/ 93 745 29 05

e-mail: [email protected]

web: www.circutor.com

(+34)

Rated voltage

Exciting current

Frequency

Exciting current duration

>

Nr. of operations

>

Switching changes

Connecting terminals

Type of protection

210 V ....230 V a.c.

1.5 A

50Hz/60Hz

20 ms

20.000

max. 12/min

Shock protected to

DIN VDE 0106,part 100

DIN 40 050 IP 20

Technical Data:

.

Connection

The MCB is equipped with open, combination-type box

terminals with multo-slot screws on the input and output

sides, permitting the connection of fine-strand or solid
conductor with a cross section of 1-25 mm . Specified

tightening torque, 2Nm.

The remote control mechanism is provided with screw

terminals, suitable for the connection of conductors up to
max. 2.5 mm .Specified tightening torque, 0.8 Nm.

2

2 .

MCB.P - WRKRT-25T diagramm connection

MCB.T - WRKRT-25T diagramm connection

LOAD

3

1

2

L3

L2

L1

N

T

R

COM

A2

2 1

A1

R1 R2

EXTERNAL

RESET

0.5

0.5

1

0.75

1

0.5

0.5

DELAY

s

A

0.02

0.1

0.3

0.3

0.1

0.3

0.3

3

0.03

POWER

T

S

T

E

E

R

T

E

S

Un 230V

Un 230V

type WRKRT-25T

type WRKRT-25T

LOAD

3

1

2

L3

L2

L1

N

T

R

COM

A2

2 1

A1

R1 R2

Auxiliary contacts

(White) COMMON
(Brown )

state inf.

ON-OFF-

RESET level
(Green ) Remote

control state inf.

EXTERNAL

RESET

0.5

1

0.75

1

0.5

DELAY

s

A

0.02

0.1

0.3

0.1

0.3

3

0.03

POWER

T

S
T

E

E

R

T

E

S

Un 230V

Un 230V

type WRKRT-25T

type WRKRT-25T

Cód: M98138201-20-03A