CCL – Sentinel 70/140 installation and operation ci0012 issue 3 6

th

May 2011 p5/6

General

Electrical connection is via screw terminal blocks on the
Sentinel circuit board.

For SNS models:-

For SNL models:-

On enclosed ESNS/ESNL models, an additional terminal
block provides convenient connection of AC supply and
DC output. The AC supply Earth must be connected to the
stud connector on the metal enclosure, as shown below.

For ESNL models:-

DC Output

Before DC connection or disconnection:-
 Ensure AC supply input is isolated.

Disconnecting the batteries while the
AC supply is live can result in sparking at
the battery terminals, ignition of battery
gasses and serious personal injury.

 Check that the charger output is compatible

with battery type & voltage. Incompatibility
may result in damage to the charger,
batteries and serious personal injury.

Connect the Sentinel output to the battery terminals,
observing the warnings above and the correct DC polarity.

The Sentinel output includes a self-resetting polyfuse
for protection of reverse polarity and short-circuit faults.
In the event of such faults, isolate the AC supply,
disconnect the output terminals and allow the fuse to reset;
replacement of the fuse should not be necessary. The
charger can then be re-connected and switched back on. If
the fuse fails to reset, return the charger to the supplier.

Auto Boost Initiate

On (E)SNL chargers, two terminals may be linked
(e.g. using an operator-controlled momentary push button
or panel switch) to give manual initiation of an Auto Boost
cycle (at any time, regardless of battery voltage).

Alarm output

All Sentinel models include a relay-based output for
remote signalling of faults. During fault conditions, the
relay de-energises and the output gives a negative DC
signal, rating 1A max. at 30 VDC.
(E)SNS models monitor charge fail faults, i.e. AC supply or
fuse failure, DC fuse failure or low/zero current output.
(E)SNL models monitor for charge fail faults, plus battery
low voltage and battery high voltage.
The alarm relay de-energises immediately on detection of
a charge fail fault, and 120 sec after detection of low or
high battery voltage faults (to allow for normal voltage
variations, e.g. during engine cranking).

AC Input (power supply)

Before AC connection, disconnection or fuse
replacement:-
 Isolate the AC supply
 Ensure a good earth connection to the earth

stud on the charger’s metal chassis.

 Ensure the AC supply voltage is compatible

with the charger’s supply rating. Exceeding
the rated voltage may result in damage
to the charger and connected equipment,
and cause serious personal injury.

All Sentinel models are fitted with mains AC input fuses,
with ratings as labelled on each charger.

ELECTRICAL CONNECTION

DANGER !

HIGH VOLTS

WARNING: DANGER OF INJURY OR DEATH. During normal operation, Sentinel is
connected to high voltage AC circuits. Before connection, disconnection or handling of
these chargers, ensure isolation of all AC power supplies. Connection or disconnection
with live wiring can also cause hazardous sparking and component damage.