LOAD

See datasheet for VitessePlus marshalling box

SUPPLY VOLTAGE

12VDC

TIME OUT PERIOD

Adjustable 10 seconds to 99 minutes

LIGHT LEVEL

Light to dark

FIXING METHOD

Spring fixing, or surface fixing using additional Part No. MWS3A-DBB

(Surface mounting box)

MATERIAL

Flame retardant ABS

TYPE

Class 2

TEMPERATURE

-10°C to 35°C

CONFORMITY

EMC-89/336/EEC

LVD-73/23/EEC

VITP-MWS3A VitessePlus microwave presence detector
MWS3A-DBB

Surface mounting box

VITP-MB

VitessePlus marshalling box (non-dimming)

VITP-MBDSI

VitessePlus dimming marshalling box DSI (digital dimming)

VITP-MBDALI VitessePlus dimming marshalling box DALI (digital dimming)
VITP-MBD

VitessePlus dimming marshalling box 1-10V (analogue dimming)

UHS

User handset with on/off override and lux up / lux down adjustment

UHS3

User handset with on/off override and cancel only

UHS3/2

User handset with off override and cancel only

DD-LCDHS

IR remote control programming handset with LCD
screen

11. Specification

12. Part Numbers

LIGHTS DO NOT COME ON

Check to see if the Vitesse Plus marshalling
box is powered up and the wiring is correct.
Disconnect both RJ45 connections on the Cat
5 patch lead and re-connect, ensuring that
they ―click‖ into position, making good
connection.
Check that the ―lux hold off‖ setting is not
keeping the lights off because there is
sufficient ambient light.
If the detection range is smaller than
expected, check the diagram on page 11.
If the LED is flashing at regular intervals, this
shows that the detector is being overridden.
Press the cancel button on the handset.

LIGHTS DO NOT GO OFF

Ensure that the area is left unoccupied for
longer than the selected timer setting.
Make sure that the sensor is not adjacent to
circulating air, heaters or lamps.
If the LED is flashing at regular intervals, this
shows that the detector is being overridden
on. Press the cancel button on the handset.

10. Fault finding

Ref %WD307 Issue 2

C.P. Electronics Ltd
Brent Crescent
London
NW10 7XR
United Kingdom
Tel:

+ 44 (0) 333 900 0671

Fax:

+ 44 (0) 333 900 0674

www.cpelectronics.co.uk
[email protected]

IMPORTANT NOTICE!
This device should be installed by a qualified electrician in
accordance with the latest edition of the IEE wiring regulations.

Due to our policy of continual product improvement CP Electronics reserves the right
to alter the specification of this product without prior notice.

FM 45789

EMS 534520

Section

Contents

Page

1

Dimensional information

1

2

Description and operation

2

3

Fixing and wiring

3

4

Fixing - Flush

4

5

Fixing - surface

4

6

Head locking

5

7

Time, lux & sensitivity adjusters

5

8

Programming

6

9

Detection pattern diagrams

11

10

Fault finding

12

11

Specification