CP Electronics VITP-PD User Manual

Page 2

Advertising
background image

LOAD

See datasheet for Vitesse Plus marshalling box

SUPPLY VOLTAGE

12VDC

TIME OUT PERIOD

Adjustable 10 seconds to 30 minutes

LIGHT LEVEL

Light to dark

FIXING METHOD

Flush fixing in 64mm hole

MATERIAL

Flame retardant ABS

TYPE

Class 2

TEMPERATURE

-10°C to 35°C

CONFORMITY

EMC-89/336/EEC

LVD-73/23/EEC

LOAD DOES NOT COME ON

Check to see if the Vitesse Plus marshalling
box is powered up and the wiring is correct.

If the supply and wiring are good, check the
LUX level setting. Increase the LUX level set-
ting to allow the controller to turn on at higher
ambient natural light level.

If the detection range is smaller than expected,
check the diagram above. Rotating the sensor
slightly may improve the range.

LIGHTS DO NOT GO OFF

Ensure that the area is left unoccupied for
longer than the selected timer setting.

Make sure that the sensor is not adjacent to
circulating air, heaters or lamps.

Part Numbers

Fault Finding

Specification

Detection Pattern

VITP-PD

Vitesse Plus ceiling mounted presence detector

DBB

Surface mounting box

Ref #WD156 Issue 4

C.P. Electronics Ltd
Brent Crescent
London
NW10 7XR
United Kingdom
Tel:

+ 44 (0) 333 900 0671

Fax:

+ 44 (0) 333 900 0674

www.cpelectronics.co.uk
[email protected]

IMPORTANT NOTICE!
This device should be installed by a
qualified electrician in accordance with
the latest edition of the IEE wiring
regulations.

Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice.

FM 45789

EMS 534520

Advertising