CP Electronics EBDSPIR-DD-LV User Manual

Pir p

Advertising
background image

page 12

LOAD
Channel 1 (switching):
-LV

Low voltage supply with relay output rating 16A resistive 10A inductive

-LV/GOLD

Low voltage with relay contact for low on resistance suitable for control wire applications 3
Amp resistive load. Not suitable for inductive loads

-LV/OC

Low voltage supply with open collector output, rating 50mA, 30VDC max

Channel 2 (dimming):
Maximum number of DSI or DALI ballasts is 10 unless the relay is disabled then it is 20.

SUPPLY VOLTAGE

Min 11.5VDC max 36VDC, min 10VAC max 26.5VAC

TIME OUT PERIOD

Adjustable 10 seconds to 99 minutes

LIGHT LEVEL

Light to dark

TERMINAL CAPACITY 2.5mm

2

MATERIAL

Flame retardant ABS

TYPE

Class 2

TEMPERATURE

-10°C to 35°C

CONFORMITY

EMC-89/336/EEC

LVD-73/23/EEC


10. P

ART

N

UMBERS

9. S

PECIFICATION

EBDSPIR-DD-LV

PIR presence detector with relay output

EBDSPIR-DD-LV/ABS

PIR absence detector with relay output

EBDSPIR-DD-LV/PRG

PIR detector pre-commissioned (contact sales department)

EBDSPIR-DD-LV/GOLD

PIR presence detector with relay output for low current

EBDSPIR-DD-LV/GOLD/ABS PIR absence detector with relay output for low current
EBDSPIR-DD-LV/GOLD/PRG PIR detector pre-commissioned with relay output for low current (contact

sales department)

EBDSPIR-DD-LV/OC

PIR presence detector with open collector output

EBDSPIR-DD-LV/OC/ABS

PIR absence detector with open collector output

EBDSPIR-DD-LV/OC/PRG

PIR detector pre-commissioned with open collector output (contact sales
department)

DBB

Surface mounting box

DD-LCDHS

IR remote control programming handset with LCD screen

UHS

IR remote control user handset with lux and scene setting functionality

UHS3

IR remote control user handset with on/off override only

IMPORTANT NOTICE!
This device should be installed by a quali-
fied electrician in accordance with the latest
edition of the IEE wiring regulations.

C.P. Electronics Ltd
Unit 2 Abbey Manufacturing Estate
Mount Pleasant, Wembley
Middlesex. HA0 1RR


Tel:

+ 44 (0) 333 900 0671

Fax:

+ 44 (0) 333 900 0674

www.cpelectronics.co.uk

Due to our policy of continual product improvement CP Electronics reserves
the right to alter the specification of this product without prior notice.

Ref %WD303 Issue 1

page

PRODUCT DATA AND INSTALLATION SHEET

EBDSPIR-DD-LV D

IRECT

D

IM

PIR

P

RESENCE

/A

BSENCE

D

ETECTOR

1. D

IMENSIONS

C

ONTENTS

Section

Contents

Page

1

Dimensional information

1

2

Description and operation

2

3

Wiring and fixing

3

5

Programming

6

6

Wiring diagrams

8

7

Detection pattern diagrams

11

8

Fault finding

11

9

Specification

12

10

Part numbers

12

Advertising