4

Dimming Channel 2 functions EBMPIR-DD & -AD only (factory default in brackets):

4.1

Light level

Maintained illuminance level (adjustable between 1 and 999). At 999 the

output will be always be at maximum.

4.2

Presence detection

Auto switch on with detection, auto off after movement ceases and

time delay ends.

4.3 Switch level on (9)

Lux level setting to prevent the luminaires being switched on if the

ambient light level is sufficient (adjustable between 1 and 9). The

luminaires will always be switched on at level 9. For a higher resolution of

‗switch level on‘ a scale of 101-199 is available in the ‗Special menu‘.

4.4 Switch level off (9)

Lux level setting to switch the luminaires off during occupancy if the

ambient light level goes above the setting (adjustable between 1 and 9).

Level 9 will always keep the lights on. This setting can be used for

―window row switching‖. For a higher resolution of ‗switch level on‘ a scale

of 101-199 is available in the ‗Special menu‘.

4.5

DSI (default)

Selects DSI dimming (not applicable on EBMPIR-AD)

4.6

DALI

Selects DALI dimming (not applicable on EBMPIR-AD)

4.7

Memorise (N)

If this is set to Yes, the last manual lux level set will be memorised and

used as the new switch on level.

4.8

On value (99)

Dimming output level when switched on (0-99).

4.9

Off value (0)

Dimming output level when switched off (0-99). If a non-zero off value is

set, then the output will toggle between this value and completely off

depending on the switch level on and off values. For example, if it is light

outside, the fittings will be off if there is no occupancy. If it is dark outside,

they will adopt the preset off value. This feature is only enabled if ‗Min

value‘ is set to 99.

4.10 Fade value (10)

After occupancy ceases, this dimming output level is loaded for the fade

time (adjustable between 0 and 99).

4.11 Fade mins (0)

This is the time period (adjustable between 0 and 99 minutes) that the

luminaire will be held at the fade value before turning off. A value of 0

disables the fade function.

4.12 Max value (99)

Maximum dimming output level (adjustable between 0 and 99).

4.13 Min value (1)

Minimum dimming output level (adjustable between 0 and 99).

4.14 Speed on (40)

Determines the dimming response speed after the setup time has

finished. Measured in 0.1 sec intervals.

4.15 Speed set (5)

Determines the dimming response speed during the set up time.

Measured in 0.1 sec intervals. If set to 0 will disable dimming for ―Set

seconds‖ below, used if fittings are required to warm up before dimming.

4.16 Set seconds (120)

Determines how long the dimming response set-up period lasts on power-

up or on setting change (adjustable between 1 and 999 seconds). This

enables the desired lux level to be achieved rapidly when the lights come

on, or during setup.

4.17 Burn-in (0)

Determines how long the output will be at 100% so that lamps ‗burn-

in‘ (adjustable between 1 and 999 hours). The ‘burn-in‘ time is not affected

by power supply interruptions. To disable burn-in set to 0.

4.18 DALI on (off)

Provides a permanent voltage to DALI ballasts when DALI has not been

implemented correctly in the ballast. Maximum number of ballasts is 4

unless the relay is disabled then it is 10. This is a Special menu option.

5

User Menu

DD-LCDHS user menu or UHS handset functions:

5.1

Lux up

Increase light level. Reverts when occupancy cycle complete.

5.2

Lux down

Decrease light level. Reverts when occupancy cycle complete.

5.3

Scene up

Steps up between 6 pre-defined scenes.

5.4

Scene down

Steps down between 6 pre-defined scenes.

5.5

Scene#

Select the individual scene, between 0 and 6. (1 = min. output; 2 = 10%;

3 = 25%; 4 = 50%; 5 = 75%; 6 = 100%)

5.6

Override on

Permanently overrides the luminaire output on.

5.7

Override off

Permanently overrides the luminaire output off.

5.8

Cancel

Cancels the on or off override, returning the detector to normal operation.

5.9

Set

If sent before using lux up or lux down, it will set the light level as in 4.1