Installation procedures – Pinnacle Systems SS User Manual

Page 19

Advertising
background image

- A - 11 -

Installation Procedures

Model SS Safety Light Curtain

Wiring

Emitter Pylon

Terminal#

Connector

Defi nition

1

Black

Ground

2

Red

+24vdc regulated input

3

White

CAN_L data network

4

Green

CAN_H data network

Each pylon comes standard with 21’ (6400mm) of cable
with a quick disconnect in-line connector

Optional longer cables can be purchased (to replace the
20’ (6096mm) section). Voltages applied are to never
exceed 24vdc.

Terminal#

Defi nition

1

+24vdc regulated input

2

Ground

3

CAN_H data network

4

CAN_L data network

Optional RSD

WARNING: You must wire both Outputs 1 & 2 to a
“Safety Relay Module Control Reliable” Safety PLC,
when this product is used for safety guarding.

Wire all the Grounds together to the power supply.

Wire all the 24vdc together to the power supply.

Wire all the CAN_H together

Wire all the CAN_L together

Wire Output 1 and Output 2 to the “Safety Relay Module”
(see manufactures installed instructions)

Table 2a: Emitter Pylon Wiring

Table 2b: Receiver Wire Colors

Table 2c: Optional RSD

IMPORTANT: OUTPUTS 1 & 2 MUST BE USED
WITH EITHER “CONTROL RELIABLE” PLC INPUT
CIRCUITS OR A SAFETY RELAY MODULE.

Multiple Pylon Model SS Guard System

Multiple SS Guards scanning sequentially to
prevent interference with each other.

-MP Blocking one unit will not affect the others
connected together. You must have Safety Relays
for each SS Guard. If the separate SS guards are
NOT connected together via the CAN data network,
they scan independently and act as standard SS
guards.

-MP# Blocking one unit will shut off the outputs of
ALL units connected together. This allows 3 SS
guards to interface with 1 set of Safety Relays. If
the separate SS units are NOT connected together
via the CAN data network, ALL SS units will fault out
as a safety measure. # is the number of SS guards.
(See wiring diagram A-13 28-149)

All RED wires connect together and then connect to

+24vdc power supply

All BLACK wires connect together and then connect

to

GROUND

All ORANGE wires connect together and then
throughthe N.C. contacts of both Safety Relays
to GROUND

All PINK wires connect together

All WHITE wires connect together

Connect the GREEN wires together from Emitter
and Receiver of 1 SS Guard. (The GREEN wires
between guards are NOT connected together.)

Receiver Wire Colors

Terminal#

Connector

Defi nition

1

Red

+24vdc regulated input

2

Black

Ground

3

White

CAN_L data network

4

Green

CAN_H data network

5

Blue

Output 1 (24 vdc when

Green) (open when red)

(.25A

max)

6

Brown

Output 2 (24vdc when

Green) (open when Red)

(.24A

max)

7

Orange

EDM (GND when RED,

OPEN

when

GREEN)

8

Pink

Latching Relay Reset

(GND, then OPEN to

reset

Outputs)