UL-601(Rev. 2) Anti-Tie Down Concurrent

Operation Module

(For use with two Palm buttons or UltraTouch buttons.)

www.pinnaclesystems.com

NOTE: The following information is only for UL-601 boards marked 52-252R2.

Operation: The UL-601 takes input from 2 Palm buttons (or UltraTouch ergomonic palm buttons) and

provides a monitored Dry output contact (for your RUN circuit) which closes when both palm buttons

are activated within 1/4 sec of each other. If either button is released, the other button must also be

released before the output will close again.

Warning: Make sure the Palm Buttons are mounted in accordance to OSHA/ANSI regulations.

We have designed our equipment to the very highest
performance and safety standards known to the
current technological state of the art, as evidenced
by our U.S.A. and foreign patents issued and pending.
However, the installation, usage, suitability, and fitness
of our equipment for any purpose, known or unknown,
is interdependent upon the performance of other
equipment not manufactured, installed, secured or
maintained by Pinnacle Systems, Inc.

We cannot and do not accept responsibility for any
overall system performance when factors, such as
these, are beyond our control.

www.pinnaclesystems.com

[email protected]

[email protected]

Sales and Marketing Offices

United States
Pinnacle Systems, Inc.
P.O. Box 9305
Pittsburgh, PA 15225

Toll Free Number: 800-569-7697
Direct Number: 412-262-3950
Fax: 412-262-4055

Canada
Pinnacle Systems, Inc.
8-1734 Orangebrook Court
Pickering, Ontario L1W 3G8

Toll Free Number: 888-285-8885
Direct Number: 905-831-1111
Fax: 905-831-4064

Customer Service: (630) 443-8542

UL-601(Rev. 2) Anti-Tie Down Concurrent

Operation Module

(For use with two Palm buttons or UltraTouch buttons.)

NOTE: The following information is only for UL-601 boards marked 52-252R2

Operation: The UL-601 takes input from 2 Palm buttons (or UltraTouch ergomonic palm buttons) and provides

a monitored Dry output contact (for your RUN circuit) which closes when both palm buttons are activated within

1/4sec of each other. If either button is released, the other button must also be released before the output will
close again.
Warning: Make sure the Palm Buttons are mounted in accordance to OSHA/ANSI regulations

Terminal# Function

1

Power In (120vac LINE or optional 24vdc POS)

2

Power in (120vac Neutral or optional 24vdc NEG)

3

Earth Ground

4

+24vdc OUT to Palm Buttons

5

N.C. 24vdc IN from Palm #1

6

N.O. 24vdc IN from Palm #1

7

N.C. 24vdc IN from Palm #2

8

N.O. 24vdc IN from Palm #2

9-10

N.O. Safety Output (Dry 8A contact thru K1 & K2)

11-12

N.C. Output (Dry 8A contact thru K2)

PN# 28-153R2

Power Input: 5 watts max (120vac standard, 24vdc unit optional)

Replacement Relay: 32-047

Power Input: 5 watts max (120vac standard, 24vdc unit optional)

Replacement Relay: 32-047

4

5

6

7

8

9

10

11

12

3

2

1

Place in series

with RUN circuit

(Closes when

both buttons

activate within ¼

second)

Place in Aux

monitor circuit

(optional)

L

N

G

Supply

a

b

c

d

a

b

c

d

a & b = UltraTouch term# 1 & 2

c & d = UltraTouch term# 3 & 4

Left

Right

PN#: 28-153R3