Alarm Interface Utility Software V3.1.3

Specifications

Input Voltage

12 Volts DC

Current

750 mA maximum, Normal – 425mA

Input Contacts

10 per unit, Maximum 40

Input Selection

No jumper Voltage
Jumper Dry
Fused Inputs – 125 Volts DC / 450mA

Input

No Voltage (dry)
Voltage – AC or DC 1-24 Volts
Inputs can be Mixed

Connection

RJ45 Cable using RS485 Total 4 Units

Protocol

Scope and Motorola Comp2

Programming

PC software via RS232 9 pin connector

Repeat Message

0-4 or Change of State, with intervals of 1-59
minutes

Message

Open state and Closed state

Message Length

Each message has a maximum length of 80
characters

Pager Cap Code

Each Contact has Individual Pager ID

Message Alert Type

A,B,C or D selectable for each Contact

Approval

FCC Part 15, RoHS Compliant

Size

7.10 in x 3.52 in x 1.17 in

Warranty Life

RS232 Cable Pin Out

Null Modem (Special)
9-Pin F/F

1-nc, 2-3,3-2,4-6,6-4,5-5,7-8,8-7, 9-9

Serial Straight Through
9-Pin M/F

1-1,2-2,3-3,4-4,5-5,6-6,7-7,8-8, 9-nc

11