Instructions, Maintenance, Ordering information – Basler Electric BE3-27T User Manual

Page 2: Figures, 2 of 2

Advertising
background image

6.

Adjust the DELAY and repeat Steps 4 and 5 until you have the
desired time delay.

Undervoltage

1.

Adjust the SET and DELAY controls fully CCW.

2.

Decrease the applied sensing voltage from the nominal value
until the desired tripping voltage is reached.

3.

Slowly adjust the SET control CW until the relay trips (allow for
the 200 ms operating time).

4.

Set the DELAY control to the desired time delay and apply
nominal voltage to the relay.

5.

Step down the applied voltage from nominal to a level just
below the trip level set in Step 3 and measure the time delay.

6.

Adjust the DELAY and repeat Steps 4 and 5 until the desired
time delay is achieved.

MAINTENANCE

BE3 relays are solid-state devices that require no maintenance. In
the event that your relay requires repair, contact Basler Electric,
Highland, IL, USA for return authorization.

ORDERING INFORMATION

Figure 2 shows the BE3 style number identification chart.

FIGURES

Figure 1. BE3-27, BE3-59, BE3-27/59 AC Voltage Connections

Figure 2. BE3-27, BE3-59, BE3-27/59 Style Number Identification Chart

BE3-27T, BE3-59T, BE3-27T/59T

N

1) Single Phase
3) Three Phase

Three Wire

4) Three Phase

Four Wire

Sensing Input

Type

MODEL NO.

P

0

0

6

1

-7

5

A) 120 Vac
B) 240 Vac
C) 380 Vac
D) 480 Vac
S) Special voltage

Nominal Input Type

1

2

1) 50/60 Hz
2) 400 Hz

Frequency

N) Not required

External Power

1) Energize to trip (59T)
2) De-energize to trip (27T)
3) Energize to trip over, de-
energize to trip under (27T/59T)

Output Type

1

2

For other voltage applications, contact Basler Electric.

Voltages are line-to-line.

Publication

9319500990

Revision

E

Instructions

Date

04/14

Page

2 of 2