Instructions, Maintenance, Ordering information – Basler Electric BE3-27 User Manual

Page 2: Figures, 2 of 2

Advertising
background image

Undervoltage

Adjust the SET control fully CCW and the RESET control fully CW.

Decrease the applied sensing voltage from the nominal value until
the desired tripping voltage is reached.

Slowly adjust the SET control CW until the relay trips.

Increase the applied voltage to the desired reset level.

Slowly adjust the RESET control CCW until the relay resets.

MAINTENANCE

BE3 relays are solid-state devices that require no maintenance. In
the event that your relay requires repair, contact Basler Electric,
Highland, IL, USA for return authorization.

ORDERING INFORMATION

Figure 2 shows the BE3 style number identification chart.

FIGURES

Figure 1. BE3-27, BE3-59, BE3-27/59 AC Voltage Connections

Figure 2. BE3-27, BE3-59, BE3-27/59 Style Number Identification Chart

BE3-27, BE3-59, BE3-27/59

N

1) Single Phase
3) Three Phase

Three Wire

4) Three Phase

Four Wire

Sensing Input

Type

MODEL NO.

P

0

0

6

1

-7

4

A) 120 Vac
B) 240 Vac
C) 380 Vac
D) 480 Vac
S) Special voltage

Nominal Input Type

1

2

1) 50/60 Hz
2) 400 Hz

Frequency

N) Not required

External Power

1) Energize to trip (59)
2) De-energize to trip (27)
3) Energize to trip over, de-
energize to trip under (27/59)

Output Type

1

2

For other voltage applications, contact Basler Electric.

Voltages are line-to-line.

Publication

9319200990

Revision

E

Instructions

Date

04/14