Basler Electric BE3-59T-V User Manual

Instructions, Be3-59t-v

Advertising
background image

www.basler.com

+1 618.654.2341 (USA)

[email protected]

Model

BE3-59T-V

INTRODUCTION

The BE3-59T-V ac voltage relay provides voltage monitoring and
protection in three-phase systems. The BE3-59T-V operates when
the adjustable voltage trip point is reached. A time delay control is
provided with an adjustment of 0 to 10 seconds (relay operating
time is typically 200 milliseconds). This time delay may be used to
prevent false tripping when there are slight variations in the voltage
supply. The output relay energizes when the input signal exceeds
the trip point for the duration of the time delay. A red LED indicates
the state of the output relay. A green LED indicates the condition of
the power supply.

SPECIFICATIONS

Inputs

All units obtain operating power from the voltage sensing input.

Nominal Voltage:

100 to 120 Vac

Overload Withstand:

1.25 times nominal continuously.
2 times nominal for 3 s.

Frequency:

50, 60, or 400 Hz

Burden:

<2.5 VA per phase on single units

Setpoints

Overvoltage Range:

Adjustable 110 to 150 Vac

Repeatability:

Better than 0.5% of full span

Time Delay:

Adjustable 0 to 10 seconds

Operating Time:

200 ms typical

Differential:

Fixed 1% of nominal

Outputs

Relay Type:

D.P.D.T.

AC Rating:

250 V, 5 A, non-resistive,
1200 VA

DC Rating:

125 V, 1 A, resistive, 120 W

Mechanical Life:

5 million operations

Temperature

Operating Temperature:

0

°C (32°F) to 60°C (140°F)

Storage Temperature:

–40°C (–40°F) to 70°C (158°F)

Temperature Coefficient:

0.03% per

°C (300 ppm/°C)

Humidity

Relative Humidity:

95% non-condensing

Physical

Mounting:

DIN rail 1.38” by 0.29” (35 mm by
7.5 mm)

Case:

Complies with IEC 529, DIN 40050,
BS 5490

Case Material:

Complies with UL 94VO

Weight:

14 oz (400 g)

Size:

2.17” wide (55 mm)

AGENCY COMPLIANCE

cULus listed to UL 508 and CSA C22.2 No. 14

CE compliant

GOST-R certified per the relevant standards of Gosstandart of
Russia

OPERATION

BE3-59T-V ac voltage relays have two user-adjustable controls
labeled SET and DELAY. The SET control adjusts the relay trip
point. The DELAY control adjusts the length of time required to
operate the output relay after the trip point is exceeded. When the
monitored voltage exceeds the SET control setting (adjustable from
110 to 150 Vac), the time delay (established by the DELAY control
and adjustable from 0 to 10 seconds) begins timing down. If the
overvoltage condition persists for the duration of the time delay, the
output relay operates.

Setting Example: a BE3-59T-V relay with a nominal input rating of
130 Vac has the following settings:

SET - 130 Vac

DELAY - 4 seconds

A trip occurs when the sensing voltage rises above 130 Vac and 4
seconds elapses. Reset occurs when the voltage decreases below
1% of nominal below setpoint.

INSTALLATION

BE3 ac voltage relays are designed for mounting on standard DIN
rails that comply to DIN-EN 50022. Mounting involves hooking the
top edge of the cutout on the base of the case over one edge of the
DIN rail. The opposite side of the cutout containing the release clip
is then pushed over the opposite side of the DIN rail. To remove or
reposition the relay, lever the release clip and move the relay as
required. BE3 relays should be installed in a dry, vibration-free
location where the ambient temperature does not exceed the
operating temperature range. Connections to the relay should be
made using wire that meets applicable codes and is properly sized
for the application. Figures 1, 2, and 3 show the connection
terminals for the BE3-59T-V relay.

CALIBRATION

The calibration marks on the faceplate have a maximum error of
10% and are provided only as guides. Proper calibration requires
using an accurate voltmeter in parallel with the input signal. Use the
following procedure to calibrate your relay.

Overvoltage

1.

Adjust the SET control fully clockwise (CW) and the DELAY
control fully counterclockwise (CCW).

2.

Apply the desired trip voltage to the relay.

3.

Slowly (allow for the 200 ms operating time) adjust the SET
control CCW until the relay trips.

4.

Reduce the trip voltage from the relay and set the DELAY
control to the desired time delay.

5.

Apply the trip voltage to the relay and measure the time to trip.

6.

Adjust the DELAY and repeat Steps 4 and 5 until you have the
desired time delay.

MAINTENANCE

BE3 relays are solid-state devices that require no maintenance. In
the event that your relay requires repair, contact Basler Electric,
Highland, IL, USA for return authorization.

ORDERING INFORMATION

Figure 4 shows the BE3 style number identification chart.

Publication

9319600990

Revision

C

Instructions

Date

04/14

Copyright

2014