Basler Electric BE3-81O User Manual

Instructions

Advertising
background image

www.basler.com

+1 618.654.2341 (USA)

[email protected]

Model

BE3-81O, BE3-81U,

and BE3-81O/U

INTRODUCTION

BE3 frequency relays provide frequency monitoring and
protection in both single- and three-phase systems. They
are used in applications such as utility mains failure,
regulation of power supplies, and to protect generators
against over or underspeed. Underfrequency,
overfrequency, and combined under/overfrequency units are
available. BE3 frequency relays operate when the
adjustable trip point is reached. A reset control is provided
with an adjustment of 0.3 to 3.0% on 50 or 60 hertz units
and 3 to 30% on 400 hertz units. Reset ensures that the
measured parameter returns to the percent set above or
below the trip point before the relay returns to the original
state. On overfrequency units, the output relay energizes
when the input signal exceeds the trip point. On
underfrequency units, the output relay de-energizes when
the input signal goes below the trip point. A red LED
indicates the state of the relay. A green LED indicates the
condition of the power supply.

SPECIFICATIONS

Operating Power

All units are self powered.

Nominal Voltage:

120 Vac, 240 Vac, 380 Vac,
or 480 Vac

Frequency:

50 Hz, 60 Hz, or 400 Hz

Burden:

<2.5 VA per phase

Overload:

1.25 times nominal continuously.
2 times nominal for 3 s.

Setpoint

Over/Underfrequency Set Range

50 Hz Nominal:

Adjustable 40 to 60 Hz

60 Hz Nominal:

Adjustable 50 to 70 Hz

400 Hz Nominal:

Adjustable 360 to 440 Hz

Over/Underfrequency Reset Range

50 Hz Nominal:

Adjustable 0.3 to 3.0 Hz

60 Hz Nominal:

Adjustable 0.3 to 3.0 Hz

400 Hz Nominal:

Adjustable 3.0 to 30 Hz

Setpoint range accuracy is

±3%.

Repeatability

Greater than 0.5% of full span

Operating Time

200 ms typical

Output

Relay Type:

D.P.D.T.

AC Rating:

250 V, 5 A, non-resistive,
1,200 VA

DC Rating:

125 V, 1 A, resistive, 120 W

Mechanical Life:

5 million operations

Temperature

Operating Temperature:

0°C (32°F) to 60°C (140°F)

Functional Temperature: –25°C (–13°F) to 70°C (158°F)

Storage Temperature:

–40°C (–40°F) to 70°C (158°F)

Temperature Coefficient: 0.03% per °C (300 ppm/°C)

Humidity

Relative Humidity:

95% non-condensing

Physical

Mounting:

DIN rail 1.38” by 0.29” (35 mm by
7.5 mm)

Case:

Complies with IEC 529, DIN
40050, BS 5490

Case Material:

Complies with UL 94VO

Weight

Single Function:

0.88 lb (0.4 kg)

Multiple Function:

1.32 lb (0.6 kg)

Size

Single Function:

2.17” wide (55 mm)

Multiple Function:

3.93” wide (100 mm)

Agency

cULus listed to UL 508 and CSA C22.2 No. 14

CE compliant

GOST-R certified per the relevant standards of Gosstandart
of Russia

OPERATION

BE3-81O and BE3-81U frequency relays have two user-
adjustable controls marked SET and RESET. The BE3-
81O/U has four controls: UNDER SET, OVER SET, UNDER
RESET, and OVER RESET. Each SET control adjusts a
relay trip point. An overfrequency trip causes the relay
output to energize when the frequency rises above the SET
threshold. An underfrequency trip causes the relay output to
de-energize when the frequency decreases below the SET
threshold. Refer to the setpoint specifications for
overfrequency and underfrequency adjustment ranges. The
RESET control adjusts the difference between the nominal
input frequency and the reset frequency. An overfrequency
reset occurs when the frequency decreases below the
RESET setting. The overfrequency RESET setting is set as
the percentage above F

nom

where the relay will reset. An

underfrequency reset occurs when the frequency increases
above the RESET setting. The underfrequency RESET
setting is set as the percentage below F

nom

where the relay

will reset. Refer to the setpoint specifications for the
underfrequency and overfrequency RESET setting ranges.

Setting Example

A BE3-81O relay with a nominal input rating of 60 Hz has
the following settings:

SET - 65 Hz

RESET - 2 Hz

Publication

9321500990

Revision

C

Instructions

Date

04/14

Copyright