Instructions – Basler Electric BE350 User Manual

Page 3

Advertising
background image

Publication

9166800893

Revision

-

Instructions

Date

09/10

Page

3 of 4

6.

Verify the corner frequency setting by slowly reducing

the generator frequency until the generator output

voltage just starts to decrease.
If adjustment of the corner frequency is required:
a.

Rotate the Underfrequency control fully counter-

clockwise.

b.

Reduce the generator frequency from nominal

(either 50 Hz or 60 Hz) to the desired corner

frequency.

c.

Slowly adjust the Underfrequency control clock-

wise until the generator output voltage just starts

to decrease.

Figure 1. Potentiometer Controls


Figure 2. Jumper Locations


Figure 3. Frequency Compensation Characteristics