Publication

9166800995

Revision

E

Instructions

Date

03/11

Copyright

2011

www.basler.com

+1 618.654.2341 (USA)

[email protected]

Model

VR63-4A/UL

Part Number

9166800995

INTRODUCTION
The VR63-4A/UL voltage regulator is designed for use on

50/60 Hz brushless generators. Regulator features include

frequency compensation, overexcitation shutdown, a solid-

state buildup circuit, and EMI filtering.
SPECIFICATIONS
Power Input

Range:

190 to 240 Vac, ±10%,

1-phase

Frequency:

50/60 Hz

Burden:

500 VA

Sensing Input

Configuration:

1-phase

Frequency:

50/60 Hz

Range:

100 to 120 Vac, ±10%

Burden:

1 VA

Power Output

Maximum Continuous:

4 Adc, 63 Vdc, 252 W

Ratings

One Minute Forcing:

7 Adc, 100 Vdc, 700 W

Minimum:

15 Ω

DC Field Resistance Rating

Maximum:

100 Ω

Voltage Adjustment

90 to 132 Vac
Regulation Accuracy

Better than ±1% no load to full load.
Response Time
<1.5 cycles for a ±5% change in sensing voltage.
EMI Suppression
Internal electromagnetic interference filter (EMI filter).
Overexcitation Shutdown
Output power is removed under the following conditions:

Exciter field voltage exceeds 100 Vdc ±5 Vdc for a time

inversely proportional to voltage magnitude, or within 0.2

seconds if the exciter field voltage exceeds 135 Vdc

±

5 Vdc.

Voltage Buildup
Internal provisions for automatic voltage buildup from

generator residual voltages as low as 10 Vac.
Power Dissipation

8 W maximum
Temperature

Operating:

–40 to 60°C (–40 to 140°F)

Storage:

–65 to 85°C (–85 to 185°F)

Vibration

Withstands the following:

2 to 26 Hz:

1.3 G

26 to 50 Hz:

0.036 inch double amplitude

50 to 500 Hz:

5.0 G

Shock
Withstands 15 G in each of three mutually perpendicular

planes.
Weight

0.88 lb (0.4 kg)
Agencies

CSA Approved

UL Recognized

GOST-R Certified
FUNCTIONAL DESCRIPTION
Frequency Compensation
The frequency compensation characteristic of Figure 1 is

used to improve system load pickup performance by

restraining voltage recovery until frequency has also

started to recover.
The regulator is shipped from the factory set at a 45-Hz

corner frequency for 50 Hz systems. For 60 Hz systems, a

55-Hz corner frequency is achieved by removing the

jumper from the HZ terminals.
Overexcitation Shutdown
If the exciter field voltage exceeds 100 Vdc ±5 Vdc, the

regulator automatically removes the field current after a

time delay. The time delay is inversely proportional to the

magnitude of the detected overvoltage condition up to the

135 ±5 Vdc point. Beyond 135 Vdc ±5 Vdc, the field

voltage is removed within 0.2 seconds. See Figure 2.
After shutdown, reset the regulator by decreasing the

voltage below 6 Vac either by stopping the prime mover or

by interrupting the regulator input with a reset switch for 2

seconds minimum.
INSTALLATION
Mounting
The regulator may be mounted on the generator in any

convenient position (optimum cooling occurs with the long

side of the regulator vertical). Refer to the drilling diagram

of Figure 3.
Exciter Field Power Circuit
Connect regulator terminal F+ to the brushless exciter field

terminal F+, and terminal F– to terminal F–.

CAUTION

The dc resistance of the exciter field must be

greater than or equal to 15 Ω and less than

100 Ω.


Power/Sensing Input Circuit
Connect as shown in Figures 4 and 5. Power for the

exciter field and regulator circuitry is derived from the

generator output or auxiliary winding. The operable power

input range is 190 to 240 Vac.