INSTALLATION

Warning!

Perform the discharging procedure before
handling the ESD202.


An ESD202 should be used with a single circuit
breaker. Control of more than one breaker (or other
devices) by a single ESD202 is not recommended. If
control of more than one breaker is desired, it must be
demonstrated, through independent testing, that
combinations of breakers (or other devices) can be
reliably operated from a single ESD202.

Mounting

ESD202 mounting dimensions are illustrated in Figure
1. Dimensions are given in inches with millimeters in
parenthesis.

Connections

Typical ESD202 connections are shown in Figure 2.

ESD202 terminals accommodate a maximum wire
size of 12 AWG (3.31 mm

2

). The terminal screws have

a maximum torque rating of 9 in-lb (1 N

m).

STORAGE AND MAINTENANCE

This device contains long-life, aluminum electrolytic
capacitors. For devices that are not in service (spares
in storage), the life of these capacitors can be
maximized by energizing the device for 30 minutes
once per year.

No maintenance of the ESD202 is required other than
periodically checking that all connections are clean
and tight. The ESD202 is not field repairable. If repairs
are required, return the ESD202 to Basler Electric.





Figure 1. ESD202 Mounting Dimensions

Figure 2. ESD202 Typical Connections