Installation Instructions


Power Supply Connection

The 5-pin CAGE CLAMP plug connector and mounting flange illustrated is
located on the PC housing in order to connect the power supply.

Socket at the PC housing

Technical data

Connecting socket

Number of contacts

5

Contact spacing

5 mm

Minimum conductor cross-section

1.5 mm²

Minimum conductor cross-section

(AWG)

16

Rated voltage (EN)

250 V

Rated voltage (CSA)

300 V

Current EN [A]

12 A

Current CSA [A]

15 A

Length of stripped conductor

8 to 9 mm


Supplied mains power unit The Industrial PC is either fitted with a 100-240 V, 50-60 Hz power supply

unit (standard) or with a 24 V

DC

power supply unit (with the option of an

uninterruptible power supply, UPS).


Current carrying capacity of the 100-240 V power supply
unit


Current carrying capacity
of the 100-240 V power
supply unit

Output voltages from

the 100-240 V power

supply unit

Current loading
maximum

+3.3 V

20 A

+5 V stand by

2 A

+5 V

25 A

-5 V

0.3 A

+12 V

13 A

-12 V

0.8 A



Current carrying capacity of the 24 V power supply unit

Current carrying capacity
of the 24 V power supply
unit

Output voltages from

the 24 V power supply

unit

Current loading
maximum

+5 V

25 A

-5 V

1 A

+12 V

10 A

-12 V

1.5 A