BECKHOFF KL1002 User Manual

BECKHOFF Equipment

Advertising
background image

Data sheet for KL1002 and KL1012, Version 1.3

Beckhoff

®

and TwinCAT

®

are Beckhoff brands. Information is subject to change and are only binding if agreed contractually.

Beckhoff Automation GmbH, Eiserstr. 5, 33415 Verl, Germany, Tel.: +49 (0) 5246 963 0, Fax.: +49 (0) 5246 963 149, http://www.beckhoff.com

Two-channel, digital input terminals, 24 V

DC

The KL1002 and KL1012 digital input terminals acquire the binary control signals from the process level and transmit
them, in an electrically isolated form, to the higher-level automation unit. The KL1002 and KL1012 versions have input
filters of different speeds. The Bus Terminals contain two channels that indicate their signal state by means of light
emitting diodes.

Technical data

KL1002/KS1002

KL1012/KS1012

Connection technology

4-wire

Number of inputs

2

Rated voltage

24 V

DC

(-15%/+20%)

Signal voltage “0”

-3 V … +5 V

Signal voltage “1”

+15 V … +30 V

Input filter

3 ms

0.2 ms

Input current

typically 5 mA

Current consumption from K-bus

typically 3 mA

Electrical isolation

500 V (K-Bus/field potential)

Bit width in process image

2 input bits

Configuration

no address-or configuration settings required

Dimensions (W x H x D)

15mm x 100mm x 70mm (connected width: 12mm)

Weight

approx. 50 g

during operation

-25°C ... +60°C

0°C ... +55°C (according to cULus, for Canada and USA)

0°C ... +55°C (according to ATEX, see special conditions)

Permissible ambient
temperature range

during storage

-40°C... +85°C

Relative humidity

5% ... 95%, no condensation

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC resistance/emission

conforms to EN 61000-6-2 / EN 61000-6-4

Advertising
This manual is related to the following products: