Notes about operation in potentially explosive areas

EtherCAT Box Modules in potentially explosive areas

5

2 Notes about operation in potentially explosive

areas

2.1 Special conditions

Observe the special conditions for the intended use of Beckhoff fieldbus
components in potentially explosive areas (directive 94/9/EU)!

WARNING

 The certified components are to be installed in a protection enclosure

according to chapter 3 that guarantees a protection against mechanical
hazards!

 If the temperatures during rated operation are higher than 70 °C at the feed-in

points of cables, lines or pipes, or higher than 80 °C at the wire branching
points, then cables must be selected whose temperature data correspond to
the actual measured temperature values!

 Observe

the permissible ambient temperature range of 0 - 55°C for the use of

EtherCAT Box modules in potentially explosive areas!

 Measures must be taken to protect against the rated operating voltage being

exceeded by more than 40 % due to short-term interference voltages!

 The connections of the certified components may only be connected or

disconnected if the supply voltage has been switched off or if a non-explosive
atmosphere is ensured!

The fundamental health and safety requirements are fulfilled by compliance with the following standards:

EN 60079-0: 2006

EN 60079-15: 2005