BECKHOFF AX2090-NF50 User Manual

Technical data, Technical documentation, Mains filter

Advertising
background image

Technical documentation

1.0
2014­11­21
EN
TDmlAX­2090­0000­0400

Version:
Date:
Language:
Order No.:

Beckhoff Automation GmbH
Eiserstr. 5
33415 Verl
Germany

Phone:  +49(0)5246/963­0
Fax: 

+49(0)5246/963­198

[email protected]
www.beckhoff.com

Please read carefully before commissioning!

AX2090­NF50 (for AX5160­AX5193)

Appropriate use

The mains filters of the series “AX2090­NF50“ are exclusively intended for application in the control cabinet as
power supply unit of the AX5000. The filters are installed together with the servo drive as components in electrical
systems and machinery and may only be used in this way.

Safety rules and Personnel qualification

This description is only intended for trained specialists in control, automation and drive engineering who are familiar
with the applicable national standards. Knowledge of machine safety legislation is compulsory.

The responsible staff must ensure that the application or use of the products described satisfy all the requirements
for safety, including all the relevant laws, regulations and guidelines.

DANGER

Serious risk of injury through electric shock!

Even when the AX5000 is disconnected from the mains voltage, dangerous voltage continues to
be present at the "X02" terminals of the DC link: AX5160/AX5172 = 15 min., AX5190/AX5191 =
30 min. and AX5192/AX5193 = 45min.. Never touch the terminals within this period.

WARNING

Risk of injury!

Electronic equipment is not fail­safe. The machine manufacturer is responsible for ensuring that
the connected motors and the machine are brought into a safe state in the event of a fault in the
drive system.

Technical data

AX2090­NF50­

Data

0063

0100

0150

0180

Rated voltage [V AC]

480 +10%

Rated frequency [Hz]

50 / 60

Rated current [A]

63

100

150

180

Ambient temperature [°C]

45

Relative air humidity

15%...85%, Condensation not permitted

Permissible contamination

P2 to EN 61558­1

Storage and transport temperature [°C]

­25...+70 / ­40…+85

Mounting height [m]

1000 (with power reduction 4000)

(6% / 1000 m)

Protection

IP 20 (AX2090­NF50­0180 = IP00)

Leakage current [mA]

6,8

9,8

9,8

9,8

Weight [kg]

5,0

6,0

6,8

7,0

Listings UL/CSA

UL/CSA

UL/CSA

UL/CSA

Mains filter

Advertising
Table of contents