Bronkhorst High-Tech B.V.

EL-FLOW Prestige

9.17.084

34

Reset

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Unsigned char

R

0…5

114

115/8

0x0E68/3689

This parameter is used to reset program, counter or alarms.

Value 0: no reset
Value 1: Reset counter
Value 2: Reset alarm
Value 3: Reset counter
Value 4: Reset counter and counter off
Value 5: Reset firmware program (soft reset)

Make sure the ‘

114

Reset’ value is accepted by sending a 0 first. The ‘

114

Reset’ parameter may be disabled by the

156

Reset Alarm Enable’ or ‘

157

Reset Counter Enable’ parameters.

Wink

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Unsigned char [27]

W

0…9

1

0/0

0x0000/1

Any text string value between '1' and '9' lets the instrument wink (normal wink) (red and green turn by turn) for that number of

seconds for identifying its position. Default value = '0'.

Control Mode

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Unsigned int

RW

0…255

12

1/4

0x0024/37

The ‘

12

Control Mode’ is used to select different controlling modes of the instrument and determines from which sources controller

setpoints are accepted. The following control modes are available:

Value

Mode

Instrument action

Setpoint source

Slave factor

0

BUS/RS232

Normal operation, controlling

Bus or RS232

1

Analog Input

Normal operation, controlling

Analog input

2

FLOW-BUS Slave

Controlling as slave of other instrument

on bus

‘FLOW-BUS master output’ x

139

Slave Factor’ / 100%

139

Slave Factor’

3

Valve Close

Close valve

4

Controller Idle

Stand-by on bus/RS232, controlling is

stopped; Valve Output freezes in current

position

7

Setpoint 100%

Controlling at setpoint 100%

Fixed 100%

8

Valve Fully Open

Valve fully opened

9

Calibration Mode

Calibration mode enabled

(factory only)

10

Analog Slave

Controlling as slave of other instrument

on analog input

11

Analog Input’ x ‘

139

Slave

Factor’ /100%

139

Slave Factor’

12

Setpoint 0%

Controlling at setpoint 0%

Fixed 0%

13

FLOW-BUS

Analog Slave

Controlling as slave of other instrument

on bus, slave factor is set with signal on

analog input

‘FLOW-BUS master output’ x

11

Analog Input’ x ‘

139

Slave

Factor’ / 100%

11

Analog Input’

18

RS232

Normal operation, controlling

RS232