5.1.4.1

IP Configuration

As shown on the left side of

Figure 14

, the following parameters can be adjusted,

followed by a Submit:

IP Mode

Choose either Static IP (the default) or DHCP.

IP Address

Changing the default value of 192.168.92.68 is recommended.

Netmask

The default value of 255.255.255.0 is adequate for most users.

Gateway

If your Ethernet LAN has a gateway (router) enter its IP address here.

After the BASC20 has been given its initial configuration, it will be ready for use in
the full original Ethernet network. The temporary network constructed in

Figure 11

should be dismantled and the PC re-configured to restore its original IP address.

5.1.4.2

BACnet Configuration

As shown on the right side of

Figure 14

, the following parameters can be adjusted,

followed by a Submit:

Device Object Name You must change the default name (BAScontrol System) to

be unique throughout the entire BACnet internetwork.

Device Instance

This 22-bit value (0

–4,194,303) must be unique throughout the

entire BACnet internetwork. It defaults to 2749.

UDP Port

The default of 47808 should usually not be changed.

BBMD IP Address

Enter the address of the BBMD with which the BASC20 will
perform Foreign Device Registration (FDR)

— if the BBMD is

not in the same subnet as the BASC20.

BBMD Reg Time

Specify the seconds between successive FDR registrations.

5.1.4.3

Enable Protocol

On the right side of

Figure 14

, three functions can be adjusted, followed by a

Submit:

BACnet

Disabling BACnet (on by default) will free more memory for Sedona.

Sedona

Disabling Sedona (on by default) will free more memory for BACnet.

FTP

If needed, enable FTP (which by default is unchecked). If you select
FTP, BACnet and Sedona are automatically de-selected.

5.1.4.4

Authentication

On the right side of

Figure 14

, you can use up to 63 characters to specify User

Name and Password, followed by Submit:

User Name You can change the default admin to any User Name you wish.

Password

You can change the default admin to any Password you wish.

5.1.4.5

Kit Update

Consult the BASC20 support page for detailed instructions on using this feature:

www.ccontrols.com/support/bascontrol20.htm