Power Considerations

Voltage in the range of 10–36 VDC or 8–24 VAC must

deliver current commensurate with power consumption.

Power conductors can be stranded (16–18 AWG) or

solid (16–22 AWG). Zero volts and the chassis are

isolated from each other. Input connections are reverse-

polarity protected. Primary power backup for a substitute

DC supply or backup battery is possible by way of built-in

redundant diode-isolated inputs, but separate provisions

are required for charging any backup battery.

LED Indicators

To aid troubleshooting, each port LED glows solid if a link

exists, flashes to show activity and shows data rate by

colour: green for 100 Mbps and yellow for 10 Mbps. A

power LED is provided.

Network Connections

Cabling requirements appear in the table below. With

the Auto-MDIX feature, either crossover or standard

straight-through cables may be used to connect to any

copper port. When connecting fibre between one device

and another, the transmit port of one unit must connect to

the receive port of the other unit — and vice versa. Half-

duplex operation is not supported on the fibre port.

Power Options

The EICP can be

powered in various

ways as illustrated

below

: