Contemporary Control Systems BACnet Cube I/O BMT-DI10 User Manual

Digital input module bmt-di10

Advertising
background image

METZ CONNECT GmbH | Im Tal 2 | 78176 Blumberg | Germany
Phone +49 7702 533-0 | Fax +49 7702 533-433
Mounting instruction see www.metz-connect.com

1. Description

The BACnet MS/TP module with 10 digital inputs was developed for
decentralized switching tasks. It is suitable for detecting potential-free
switch states, for example electrical limit switches on vent valves or au-
xiliary contacts of power contactors. The inputs can be used as contact
or voltage inputs. The inputs can be scanned by means of standard
objects via a BACnet client. The module is addressed and the baud
rate is set by means of two address switches on the front.
Suitable for decentralized mounting in serial sub-distributor.

7622/899299-02

Digital Input Module

BMT-DI10

1108811319

2. Declaration of Conformity

The device was tested according to the applicable standards. Con-
formity was proofed. The declaration of conformity is available at
the manufacturer METZ CONNECT GmbH.

Notes Regarding Device Description

These instructions include indications for use and mounting of the
device. In case of questions that cannot be answered with these
instructions please consult supplier or manufacturer.
The indicated installation directions or rules are applicable to the
Federal Republic of Germany. If the device is used in other countries
it applies to the equipment installer or the user to meet the national
directions.

Safety Instructions

Keep the applicable directions for industrial safety and prevention of
accidents as well as the VDE rules.
Technicians and/or installers are informed that they have to
electrically discharge themselves as prescribed before installation or
maintenance of the devices.
Only qualified personnel shall do mounting and installation work with
the devices, see section “qualified personnel”.
The information of these instructions have to be read and understood
by every person using this device.

Symbols

Warning of dangerous electrical voltage
Danger

means that non-observance may cause risk of life,
grievous bodily harm or heavy material damage.

Qualified Personnel

Qualified personnel in the sense of these instructions are persons who
are well versed in the use and installation of such devices and whose
professional qualification meets the requirements of their work.
This includes for example:

• Qualification to connect the device according to the VDE

specifications and the local regulations and a qualification to put
this device into operation, to power it down or to activate it by
respecting the internal directions.

• Knowledge of safety rules.

• Knowledge about application and use of the device within the

equipment system etc.

3. Technical Data

BACnet Interface

Protocoll

BACnet MS/TP

Transmission rate

9600 to 115200 Bd

(factory setting 9600 Bd)

Cabling

RS485 two wire bus with voltage

equalizing cable in bus / line topology

terminate with 120 Ohms

Supply

Operating voltage range

20 to 28 V AC/DC (SELV)

Current consumption

85 mA (AC) / 75 mA (DC)

Relative duty cycle

100 %

Input

Input voltage

30 V DC

High-signal recognition

>7 V AC/DC

Housing

Dimensions WxHxD

1.4 x 2.8 x 2.6 in. (35 x 70 x 65 mm)

Weight

83 g

Mounting position

any

Mounting

standard rail TH35 per IEC 60715

Mounting in series

the maximum quantity of modules

without space

connected in line is limited to 15 or

to a maximum power consumption of

2 Amps (AC or DC) per connection to

the power supply. For any similar

block of additional modules a

separate connection to the power

supply is mandatory.

Material
Housing

Polyamide 6.6 V0

Terminal blocks

Polyamide 6.6 V0

Cover plate

Polycarbonate

Type of protection
(IEC 60529)
Housing

IP40

Terminal blocks

IP20

Terminal blocks

Supply and bus
4 pole terminal block

max. AWG 16 (1.5 mm²) solid wire

max. AWG 18 (1.0 mm²) stranded wire

Wire diameter

min. 0.3 mm up to max. 1.4 mm

(terminal block and jumper plug are

included to each packing unit)

Module connection
Inputs

max. AWG 12 (4.0 mm²) solid wire

max. AWG 14 (2.5 mm²) stranded wire

Wire diameter

min. 0.3 mm up to max 2.7 mm

Protective circuitry

polarity reversal protection of

operating voltage

polarity reversal protection of supply

and bus

Temperature range

Operation

-5 °C to +55 °C

Storage

-20 °C to +70 °C

Display

Operating / bus activity

green LED

Error indication

red LED

Status of the inputs

yellow LED

5. Connection Diagram

BUS A-

BUS B+

2

1

3

5

4

9

8

7

6 C1

10

A1
A2

A-

B+

A1
A2

A-

B+

GND

24 V AC/DC

C1

4. Wiring Diagram

BUS A-

BUS B+

C1

1
2
3
4
5
6
7
8
9
10

A2 /GND

A1/+24 V

BACnet MS/TP on RS-485

RISC - CPU

24 V

C1

+24 V

GND

J

Advertising