Continuation Software Description

Function Table for Binary Input

Out_Of_Service

Polarity

Binary Input

Present_Value

OUT_OF_SERVICE

0

0

0
1

0
1

0

0

1

0
1

1
0

0

1

0

0
1

x

1

1

1

0
1

x

1

x: Present_Value is writable and not affected by inputs

Input pulses must have minimum High and Low times of 30ms.

Accumulator Object 1…4

Property

Remark / Value

RW

Object_Identifier

accumulator, instance 1 … 4

R

Object_Type

ACCUMULATOR (23)

R

Object_Name

max. 42 Bytes, default “Accumulator 1” … “Accumulator 4”

RW-E

Description

max. 84 Bytes, default “”

RW-E

Present_Value

pulse counter of corresponding input,
writable if Out_Of_Service (pulse counter remains unchanged)

R-E
RW

Status_Flags

IN_ALARM: 0
FAULT: 0
OVERRIDDEN: 0
OUT_OF_SERVICE:

0 / 1

R

Event_State

NORMAL (0)

R

Out_Of_Service

FALSE (0) / TRUE (1)

RW

Max_Pres_Value

4294967295

R

Units

default no-units (95)

RW-E

Prescale

Multiplier

0 … 65535, default 1

Modulo-Divide

1 … 65535, default 1

RW-E

Scale

Float-Scale or Integer-Scale, default 1.0 (Float)

RW-E

Value_Set

pulse counter is stored to Value_Set, when corresponding key is pressed, default 0

R-E

R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash

Group Object 1…3

Property

Remark / Value

RW

Object_Identifier

group, instance 1 … 3

R

Object_Type

GROUP (11)

R

Object_Name

max. 42 Bytes, default “Group 1” … “Group 3”

RW-E

Description

max. 84 Bytes, default “”

RW-E

Present_Value

Present_Value of Binary Inputs,
see next Table

R

List_Of_Group_Members

see next Table

R

R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash

Members of Groups

Group

Binary Input
1

2

3

4

1

x

x

x

x

2

x

x

3

x

x