Contemporary Control Systems BACnet Cube I/O BMT-AO4 User Manual

Analog output module bmt-ao4

Advertising
background image

METZ CONNECT GmbH | Im Tal 2 | 78176 Blumberg | Germany
Phone +49 7702 533-0 | Fax +49 7702 533-433
Mounting instruction see www.metz-connect.com

2. Declaration of Conformity

The device was tested according to the applicable standards. Con-
formity was proofed. The declaration of conformity is available at
the manufacturer METZ CONNECT GmbH.

Notes Regarding Device Description

These instructions include indications for use and mounting of the
device. In case of questions that cannot be answered with these
instructions please consult supplier or manufacturer.
The indicated installation directions or rules are applicable to the
Federal Republic of Germany. If the device is used in other countries
it applies to the equipment installer or the user to meet the national
directions.

Safety Instructions

Keep the applicable directions for industrial safety and prevention
of accidents as well as the VDE rules.
Technicians and/or installers are informed that they have to
electrically discharge themselves as prescribed before installation or
maintenance of the devices.
Only qualified personnel shall do mounting and installation work
with the devices, see section “qualified personnel”.
The information of these instructions have to be read and under-
stood by every person using this device.

Symbols

Warning of dangerous electrical voltage
Danger

means that non-observance may cause risk of life,
grievous bodily harm or heavy material damage.

Qualified Personnel

Qualified personnel in the sense of these instructions are persons
who are well versed in the use and installation of such devices and
whose professional qualification meets the requirements of their
work.
This includes for example:

• Qualification to connect the device according to the VDE

specifications and the local regulations and a qualification to put
this device into operation, to power it down or to activate it by
respecting the internal directions.

• Knowledge of safety rules.

• Knowledge about application and use of the device within the

equipment system etc.

7628/899299-07

Analog Output Module
BMT-AO4

1108851302

1. Description

The BACnet MS/TP module with 4 analog outputs was develo-
ped for decentralized switching tasks. It is suitable as encoder for
control variables, for example for electrical vent and mixing valves,
valve positions, etc.
The outputs can be output by means of standard objects via a
BACnet client. The module is addressed and the baud rate is set by
means of two address switches on the front.
Suitable for decentralized mounting in serial sub-distributor.

3. Technical Data

BACnet Interface

Protocoll

BACnet MS/TP

Transmission rate

9600 to 115200 Bd

(factory setting 9600 Bd)

Cabling

RS485 two wire bus with voltage

equalizing cable in bus / line topology;

terminate with 120 Ohms

Supply

Operating voltage range

20 to 28 V AC/DC (SELV)

Current consumption

50 mA (AC) / 20 mA (DC)

Relative duty cycle

100 %

Output

Output voltage

4 x 0 to 10 V DC

Output current

5 mA at 10 V DC

Resolution

10 mV / Digit

Housing

Dimensions WxHxD

1.4 x 2.8 x 2.6 in. (35 x 70 x 65 mm)

Weight

72 g

Mounting position

any

Mounting

standard rail TH35 per IEC 60715

Mounting in series

the maximum quantity of modules

without space

connected in line is limited to 15 or

to a maximum power consumption

of 2 Amps (AC or DC) per connection

to the power supply. For any similar

block of additional modules a sepa-

rate connection to the power supply

is mandatory.

Material
Housing

Polyamide 6.6 V0

Terminal blocks

Polyamide 6.6 V0

Cover plate

Polycarbonate

Type of protection
(IEC 60529)
Housing

IP40

Terminal blocks

IP20

Terminal blocks

Supply and bus
4 pole terminal block

max. AWG 16 (1.5 mm²) solid wire

max. AWG 18 (1.0 mm²) stranded wire

Wire diameter

min. 0.3 mm up to max. 1.4 mm

(terminal block and jumper plug are

included to each packing unit)

Module connection
Outputs

max. AWG 12 (4.0 mm²) solid wire

max. AWG 14 (2.5 mm²) stranded wire

Wire diameter

min. 0.3 mm up to max 2.7 mm

Protective circuitry

polarity reversal protection of

operating voltage

polarity reversal protection of supply

and bus

Temperature range

Operation

-5 °C to +55 °C

Storage

-20 °C to +70 °C

Display

Operating / bus activity

green LED

Error indication

red LED

5. Connection Diagram

BUS A-

BUS B+

C2

1

C2

2

C2 4

C2 3

A1
A2

A-

B+

A1
A2

A-

B+

GND

24 V AC/DC

4. Wiring Diagram

D

A

BUS A-

BUS B+

1

A2 /GND

A1/+24 V

BACnet

MS/TP

on RS-485

RISC - CPU

24 V

C2

2
C2

3
C2

4
C2

Output:
Voltage

0-10V

Advertising