Panel Mounted Low Voltage Disconnect

DC Solid State Switches

FEATURES

Wide range of output current ratings and control set points
MOSFET DC switching technology
Industry standard package
Ambient temperature compensated

Mounting on Panel

Locate the panel section on which the LVD switch will be mounted on
Be sure to use thermal pad/grease between LVD switch and the panel
Tab holes have a diameter of 0.125 in (3.2 mm). You will need two screws no longer than that to
mount the LVD switch onto panel
Align LVD switch tabs with panel surface and screw both top and bottom sides. Recommended
torque is 20 in lb (2.2 Nm)

MOUNTING INSTRUCTIONS

Mounting on Heat Sink

Select adequate heat sink (see thermal derating curves)
Be sure to use thermal pad/grease between LVD switch and the selected heat sink
Align SSR tabs with heat sink surface and screw both top and bottom sides. Recommended
torque is 20 in lb (2.2 Nm)

Please read all installation instructions before using your LVD Series switch.
Choose one of the two mounting options and follow the instructions.

PART NUMBER NOMENCLATURE

40

75

A

LVD

Series

Max DC Output Voltage
75:
3-75 Vdc

Control Set Points
A:
18 Vdc max., Hysteresis 11.0-11.5 Vdc
B: 18 Vdc max., Hysteresis 11.5-12.0 Vdc
C: 18 Vdc max., Hysteresis 12.0-12.5 Vdc
D: 36 Vdc max., Hysteresis 23.0-24.0 Vdc
E: 36 Vdc max., Hysteresis 24.0-25.0 Vdc
F: 36 Vdc max., Hysteresis 25.6-26.6 Vdc

Output Current
40:
40 Amp

60 Amp

80: 80 Amp

60:

100: 100 Amp

Options
H:
Thermal Pad

Required for valid part number
For options only and not required

for valid part number

H

Rev: 111710

Crydom LVD Series Solid State Switches were developed to offer the advantages of Crydom’s thermal
management technology in a switch that monitors a system’s battery voltage and disconnects the battery from
the system when it’s voltage falls below a preset low voltage value.