Installation sheet, Din rail mount, Derating curves – Crydom CTR Series User Manual

Page 2: Wiring diagram

Advertising
background image

The following deating curves must be observed before installation.

DERATING CURVES

(B, C)

Load Current (Amps)

30

25

20

15

10

5

0

20

40

60

80

Ambient Temperature (ºC)

CTRx60xx

Wire Size

Maximum wire size of AWG #16 (1.3 mm

2

) on

input and AWG #8 (8.4 mm

2

) output terminals.

Connections

Ensure that wires ends are stripped to a

minimum length of 0.4 in (10 mm).

Recommended Screw Torque Range

4.4 in-lbs (0.5 Nm) on input and 12 in-lbs (1.3 Nm)

on output.

WIRING DIAGRAM

Rev: 062411

Installation Sheet

DIN Rail Mount

Advertising