Dataprobe iBoot-IO User Manual

General description, Connections

Advertising
background image

Power Switch

Contact Control

1. General Description

The iBoot-IO is a remote controlled power On / Off switch. One external control input is used to switch the
power ON and OFF. The iBoot-IO also provides a feedback circuit to verify the current power status. iBoot-IO
handles worldwide power from 105-240VAC. It is capable of switching up to 12 Amps at 120VAC and 10
Amps at 220 VAC. Screw terminals provide connection to the contact closure control and feedback circuit.
Power connections are made using supplied IEC-320 to NEMA 1-15 cables.

1.1. Covered Models

Four models are covered in this document. They differ in the type of input circuit used to control the power and
the default status of the power outlet when no control is provided.

SKU

Model

Default Power Control Input Type

1410037

iBoot-IO

ON

Dry Contact

1410039

iBoot-IO-OFF

OFF

Dry Contact

1410044

iBoot-IO-LS

ON

+3 to +12 VDC

1410045

iBoot-IO-OFFLS

OFF

+3 to +12 VDC

2. Connections

2.1. Connect Powered Device

Connect the device to be powered ON and OFF to the IEC receptacle marked Switched Outlet. An IEC 320 to
North American (NEMA 5-15) power cord is included for connecting the iBoot-G2 outlet to the device to be
controlled.

Make sure that the combined load of all controlled devices does not exceed 12 Amps for 105-
125VAC or 10 Amps for 210-240VAC.


Connect Power Mains
Connect the supplied power cord to the connector labeled AC Input, and the other end
to your AC source. If a power cord with a different terminating plug is required, be sure it is properly rated and
meets all the required local electrical standards.





Other Power Cords

Sourced Locally

Connect to Power Mains using

Supplied Cord

Connect Powered Device using

Supplied Cord