DeviceNet Network Scanner

Instruction Sheet

Warning

This Instruction Sheet only provides descriptions for electrical specifications, general specifications, installation and

wiring.

DVPDNET-SL is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust,

humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device
(e.g. key or specific tools are required for opening the enclosure) in case danger and damage on the device may
occur. Do NOT tough any terminal when the power is switched on.

Introduction

Functions:

™

Support Group 2 server device and Group 2 only
server device.

™

Support DeviceNet Master mode and Slave mode.

™

Support EDS file configure in ElinkConfigurator
software.

™

Support explicit connection via Predefined
Master/Slave Connection Set. (Explicit message)

™

Connection size is flexible from 1 to 390 bytes in
input and output area.

Nameplate Explanation

D NE T-S L 0 T62 600 00 1

M A D E I N XX X XX X

D e l t a P L C m o d e l n a m e

VX.XXXX

P o w e r i n p u t s p e c i f i c a t i o n

B a r c o d e , s e r i e s N o . , v e r s i o n

Model Name and Serial Number Explanations

Serial Number

Production series
Production week

Production year (2006)
Production plant (Taoyuan)
Serial number of version

Production Model

Product Series

For SV MCU

Model

Serial Number

Model type

For SV left side extended module

26 0001

6

T

0

DNET-SL

DVP DNET

S L

Product Profile

Unit: mm



1

Model name

2

Extension port

3

Power, MS, NS LED

4

DIN rail clip

5

Message display

6

Extension clip

7

Address switch

8

Function switch

9

DeviceNet connection port

Specifications

DeviceNet Connection

Interface

Removable connector
(5.08mm)

Transmission
method

CAN

Transmission
cable

2-wire twisted shielded cable
with 2-wire bus power cable
and drain

Electrical
isolation

500V DC

Communication

Message type

I/O polled, bit-strobe, change
of state/cyclic

Baud rates

125 Kbps; 250 Kbps;
500 Kbps

Product code

64

Product type

12

Vendor ID

799 (Delta Electronics Inc.)

Electrical Specification

Module power voltage: All other power derived from PLC controller power supply

DeviceNet

Network power input: 11 ~ 25V DC; Current: less than 50mA (25V DC)

Environment Specifications

Noise immunity

ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV,
Analog & communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV

RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m

Environment

Operation: 0ºC ~ 55ºC (temperature); 50 ~ 95% (humidity); pollution degree 2
Storage: -40 ºC ~ 70ºC (temperature); 5 ~ 95% (humidity)

Vibration/shock
resistance

Standard: IEC1131-2、IEC 68-2-6 (TEST Fc)/IEC1131-2 & IEC 68-2-27 (TEST Ea)

Approvals

Installation

Profile (Dimensions are in millimeter and [inch])

3

2

0

1

4

9

8

6

7

0

MS

NS

5

DR 0

DR 1

x10

IN 1
IN 0

DVPDNET

x10

5

3

2

4

0

1

8

6

7

9

1


Installing DVPDNET-SL With PLC MPU

DVPDNET

DVP28SV

RUN

STOP

2

2

1


Pin Definition Of DevicetNet Connection Port

Pin

Signal

Color

Content

1

V-

Black

0 VDC

2 CAN_L

Blue

Signal-

3 Drain - Shield
4 CAN_H

White

Signal+

5 V+

Red

24

VDC

1

2

3

4

5


MAC ID Setting

Switch setting

Content

0…63

Valid DeviceNet MAC ID setting

Others

Invalid DeviceNet MAC ID setting

9

1

6

4

5

0

0

9

1

3

2

7

8

2

5

6

4

3

7

8

Function Switch Setting

DR1

DR0

Baud rate

OFF OFF

125K

bps

OFF ON

250K

bps

ON OFF

500K

bps

IN0

Reserved

IN1

Reserved

Connecting DVPDNET-SL Scanner With Slave Devices

Connection Example:

PORT2

PORT1

DeviceNet

DVP-PS01

VFD-B

DNA02

DVPDT01
DVP-12SC

DVP28SV

DVPDNET-SL

DVPDNET

DVP28SV

RUN

STOP

RUN

STOP

D

V

P

-1

2

S

C

D

T

0

1

L
N

0V

Cable Length and Baud Rates

The maximum cable length in a segment depends on the transmission speed. DeviceNet communicates at

speeds from 125K bps to 500K bps over distances from 100 to 500 meters.

Baud rates (bps)

125K

250K

500K

Length (m)

500

250

100

Configuration

Access DNET Scanner With PLC

When DNET scanner is connected to PLC, it will get a data area that maps to DNET scanner in PLC.

Mapped D registers

Index of DNET

scanner

Output image table

Input image table

1

D6250 – D6497

D6000 – D6247

2

D6750 – D6997

D6500 – D6747

3

D7250 – D7497

D7000 – D7247

4

D7750 – D7997

D7500 – D7747

5

D8250 – D8497

D8000 – D8247

6

D8750 – D8997

D8500 – D8747

7

D9250 – D9497

D9000 – D9247

8

D9750 – D9997

D9500 – D9747


The index of DNET scanner is the sequence number of scanner. The 1

st

scanner is near to SV MPU and the index number is1. The 2

nd

scanner is

near to the 1

st

scanner in the left side and to be numbered as 2. The others are numbered as 3, 4, …and so on.

Advertising