2 operation – Flowserve 682 Seal Cooler User Manual

Page 7

Advertising
background image

7

It is strongly recommended that the 682 Seal Cooler be mounted in a

vertical position whenever possible for a Plan 23 to ensure proper cooling

efficiencies and simplify maintenance requirements. For applications that

must conform to API Standard 682 requirements, the API Standard 682

specifies that the seal cooler must be mounted to allow complete draining

and venting of both the cooling water and the process fluid. Vertical

installations achieve this capability but horizontal mountings do not.

2 Operation

2.1 When installing and again before start-up, ensure that the seal cooler,

piping, and vent locations provide complete venting of gas/air from both

the tube and shell systems. This requires the vents to be located at the

highest point in each system.

2.2 Before start-up, ensure that all the gas/air is vented from both the tube

and shell systems to provide the system efficiencies expected and prevent

a vapor lock condition.

2.3 When installing and again before start-up, ensure that the seal cooler,

piping, and drain locations allow for drainage of fluid from both the tube

and shell systems. This requires the drains to be located at the lowest

point in each system. A drain valve (not just a plug) should be mounted

in the shell system.

2.4 If the tube and shell systems can not be configured for both proper venting

and proper draining, as with a horizontal installation, it is more important

for proper venting be achieved.

2.5 Before start-up, ensure that all piping is properly attached to the appropri-

ate connections for both the tube and shell systems to prevent fluid leaks

and achieve expected cooler efficiencies.

2.6 At start-up, ensure that the flush fluid flow and cooling fluid flow are set

and stabilized at the prescribed flow rates determined for the application.

2.7 Do not allow the shell system cooling fluid flow rate to be operated below

24.6 L / min (6.5 gpm). Lower flow rates will encourage fouling which

reduces the seal cooler heat transfer capabilities.

2.8 Cooler performance should be monitored periodically. Baseline tempera-

tures should be gathered soon after equipment commissioning. Target

shell side base line temperature differential should be 20°F or lower.

Exceeding this temperature could result in a loss of efficiency and possibly

result in shell side fouling.

2.9 Periodically shell and tube side temperature differential should be

monitored. With no change in process temperature tube side

temperatures should be not exceed 10-20°F rise from base line.

Shell side differential exceeding 20°F or significant variation from base

line indicates loss of efficiency. Shell side fouling could be a cause and

cooler cleaning should be considered.

Advertising