Establishing Functions

Select function

Before installing and commissioning the NRGS 15-1 ascertain the settings for the
required functions.

Five functions are available:

Function 1

Electrode rod 1

Low level 1 / burner off

Electrode rod 2

Low level 2

Electrode rod 3

Timed pump control (fill control) tv= 0 – 30 sec.

Electrode rod 4

High level

Function 2

Electrode rod 1

Low level 1 / burner off with test and reset button

Electrode rod 2

Low level 2

Electrode rod 3

Timed pump control (fill control) tv= 0 – 30 sec.

Electrode rod 4

High level

Function 3

Electrode rod 1

Low level alarm 1 / burner off

Electrode rod 2

Feed pump on (fill control)

Electrode rod 3

Feed pump off (tv= 0 sec.)

Electrode rod 4

High level

Function 4

Electrode rod 1

Low level alarm 1 / burner off with test and reset button

Electrode rod 2

Feed pump on (fill control)

Electrode rod 3

Feed pump off (tv= 0 sec.)

Electrode rod 4

High level