Establishing functions, Select function – Flowserve NRGS15-1 User Manual
Page 13
13
Establishing Functions
Select function
Before installing and commissioning the NRGS 15-1 ascertain the settings for the
required functions.
Five functions are available:
Function 1
Electrode rod 1
Low level 1 / burner off
Electrode rod 2
Low level 2
Electrode rod 3
Timed pump control (fill control) tv= 0 – 30 sec.
Electrode rod 4
High level
Function 2
Electrode rod 1
Low level 1 / burner off with test and reset button
Electrode rod 2
Low level 2
Electrode rod 3
Timed pump control (fill control) tv= 0 – 30 sec.
Electrode rod 4
High level
Function 3
Electrode rod 1
Low level alarm 1 / burner off
Electrode rod 2
Feed pump on (fill control)
Electrode rod 3
Feed pump off (tv= 0 sec.)
Electrode rod 4
High level
Function 4
Electrode rod 1
Low level alarm 1 / burner off with test and reset button
Electrode rod 2
Feed pump on (fill control)
Electrode rod 3
Feed pump off (tv= 0 sec.)
Electrode rod 4
High level
ON
1 2 3
5
4
6 7 8 910
ON
1 2 3
5
4
6 7 8 910
ON
1 2 3
5
4
6 7 8 910
ON
1 2 3
5
4
6 7 8 910