System malfunctions – Flowserve NRS1-41 User Manual

Page 16

Advertising
background image

16

System Malfunctions

– continued –

LED 1 flashes slowly.

A system malfunction in the level
electrode was detected.

System Malfunction 1

LED 1 flashes slowly

Fault:

The max. admissible temperature in the terminal box of the electrode
NRG 1…-41 has been exceeded.

Remedy: Insulate electrode flange against heat radiation.

LED 1 flashes slowly

Hold down button .

LED 1 flashes slowly.

Fault:

The electronic circuit board of the level electrode NRG 1…-41 is
defective.

Remedy: Replace electronic circuit board of the level electrode.

LED 2 flashes slowly

Hold down button .

LED 2 flashes slowly.

The system will continue to work once
the causes of the system malfunction
are completely eliminated.

Danger

The terminal strip of the NRS 1-41 is live during operation. This presents
the danger of electric shock. Cut off power supply before mounting and
removing the equipment.