Worcester Controls Pulsair III Digital Electronic Positioner FCD WCAIM2056-00 - 08/04

fl owserve.com

27

Worcester Controls Pulsair III Digital Electronic Positioner FCD WCAIM2056-00 - 08/04

Full Menu: Setup

The Setup Menu is used for various settings.

FULL MENU
SETUP

The menu contents are shown in the chart on subsequent pages and the various texts

are described below:

Actuator

Type of Actuator

Rotating

Rotating actuator

Linear

Linear actuator

Size of Actuator

Time Out

Small

10 s

Medium

25 s

Large

60 s

Texas

180 s

Lever Only for linear actuator.

Lever stroke Stroke length to achieve correct display

Level cal Calibration of positions to achieve correct display

Direction

Direct Direct function (signal increase opens). Indicator/spindle rotates

counterclockwise.

Reverse Reverse function

Character

Curves that show position as a function of input signal.

Linear See

diagram

Equal % See

diagram

Quick open See

diagram

Sqr root See

diagram

Custom Create own curve.

Cust chr

# of point Specify number of points (3, 5, 9, 17, or 33)

Cust curve Enter values on X and Y axes.

Movement

Signal

y

x

Qo
Sqr
Lin
Eq%

Curr range

0% = 4.0 mA

100% = 20.0 mA Possibility of selecting which input signal values will correspond

to 0% and 100% movement respectively. Examples of settings:

• 4 mA = 0%

• 12 mA = 100%

• 12 mA = 0%

• 20 mA = 100%