Application

Usage for the intended purpose

The level electrodes NRG 6-50, NRG 7-50, NRG 9-50 and NRG -50 are used in conjunction

with level switch NRS -50 as water level limiters for steam boiler plants and (pressurised) hot water

installations.

Water level limiters switch off the heating when the water level falls below the set minimum level

(low water).

Function

When the water level falls below the low level, the level electrode is exposed and a low level alarm is

triggered in the level switch NRS -50. This switchpoint “Low water level (LW)” is determined by the

length of the electrode tip.
The self-monitoring function ensures that an alarm will also be triggered if the electrode insulation is

contaminated or has developed a leak or if there is a malfunction in the electrical connection.
The level electrode is installed inside steam boilers, vessels or inlet lines of hot-water systems. The

protective tube mounted on site (see section

Examples of Installation (pages 8, 9) ensures correct

functioning.
One level electrode NRG ...-50 can be installed together with one GESTRA level electrode, one level

switch or transmitter for water level control and high level alarm in one single protection tube or level

pot.
If the level electrode is installed in an isolatable level pot outside the boiler, make sure that the

connecting lines are rinsed regularly. In addition, the logic unit SRL is required to monitor the purging

times and the purging sequence.
If the connecting lines for steam ≥ 40 mm and water ≥ 00mm, the installation is considered to be

internal. In this case the rinsing processes do not have to be monitored.