Wiring

– continued –

Wiring diagram for control unit NRS 1-40.1

When using the control unit NRS 1-40.1 for more than two limiting functions the CAN bus
must be supplied with 24V DC by a safety power supply unit (e. g. Siemens SITOP Power 05).

The power supply unit must be in accordance with DIN VDE 0106 (safety separation) and
fused with an overcurrent protective device to EN 61010-1 / VDE 0411.

The CAN bus supply must not be connected to terminals 1 and 5.